"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Number of Triads","Diameter Over Conductor","Insulation Thickness","Jacket Thickness","Approx. OD","Approx. Weight","Min Bending Radius","DC Resistance @ 25C" "","AWG/Kcmil","triads","inches","mils","mils","inches","lbs./MFT","inches","ohm/MFT" "592114", 16,"1","0.056","30","45","0.350","75","4.2","4.181" "TBA", 16,"2","0.056","30","60","0.615","154","7.38","4.181" "595481", 16,"4","0.056","30","60","0.750","277","9.0","4.181" "595482", 16,"8","0.056","30","80","0.964","524","11.6","4.181" "TBA", 16,"12","0.056","30","80","1.209","686","14.5","4.181" "TBA", 16,"24","0.056","30","110","1.731","1364","20.8","4.181" "TBA", 16,"36","0.056","30","110","1.982","1923","23.8","4.181"