"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","inches","lbs./MFT","lbs./MFT" "569424","2","168","0","0.290","210","0.753","169","177" "587529","2","259","0","0.315","200","0.770","169","424" "569423","1/0","259","1","0.379","210","0.840","320","548" "569425","2/0","324","1","0.400","220","0.883","406","674" "569487","4/0","532","1","0.530","210","0.979","651","960" "674322","4/0","532","1","0.530","360","1.280","638","1244" "569427","350","893","1","0.670","230","1.160","1084","1475" "569428","500","1221","1","0.858","230","1.350","1514","1970" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 60C","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps","Amps" "569424","2","0","","530","0.172","0.207","0.045","95","115","130" "587529","2","0","","530","0.172","0.207","0.045","95","115","130" "569423","1/0","1","","844","0.109","0.131","0.044","125","150","170" "569425","2/0","1","","1064","0.087","0.104","0.043","145","175","195" "569487","4/0","1","","1692","0.055","0.067","0.041","195","230","260" "674322","4/0","1","","1692","0.055","0.067","0.041","195","230","260" "569427","350","1","","2800","0.033","0.042","0.040","259","310","350" "569428","500","1","","4000","0.023","0.031","0.039","320","380","430" "All dimensions are nominal and subject to normal manufacturing tolerances"