"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","inches","lbs./MFT","lbs./MFT" "TBA","20","10","0","0.036","30","0.099","3","7.09" "TBA","18","16","1","0.044","30","0.106","5","9" "F16502122C2","16","26","1","0.059","30","0.117","8","13" "F14647122C2","14","41","1","0.073","30","0.132","13","18" "F12276122C2","12","65","1","0.094","30","0.151","20","27" "F10237072C2","10","105","1","0.117","30","0.175","32","41" "TBA","8","133","1","0.153","45","0.252","51","72" "F0618907C2","6","133","1","0.198","60","0.324","81","113" "F0412707C2","4","133","1","0.235","60","0.387","129","166" "F0213312C2","2","133","1","0.290","60","0.420","210","259" "TBA","1","259","1","0.345","80","0.521","258","324" "F1T09704C2","1/0","259","1","0.390","80","0.561","326","401" "F2T1000400","2/0","259","1","0.409","80","0.585","426","513" "F3T10304C2","3/0","259","1","0.533","80","0.666","518","601" "F4T1050400","4/0","551","1","0.550","80","0.740","665","785" "TBA","250","2451","1","0.682","95","0.835","772","934" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","Amps","Amps" "TBA","20","0","0.4","8","11.319","14.725","-","-" "TBA","18","1","0.4","13","7.148","8.613","-","-","14" "F16502122C2","16","1","0.4","21","4.487","5.406","-","-","18" "F14647122C2","14","1","0.5","33","2.814","3.391","15","20","25" "F12276122C2","12","1","0.6","52","1.774","2.137","20","25","30" "F10237072C2","10","1","0.7","83","1.111","1.339","30","35","40" "TBA","8","1","1","132","0.715","0.861","40","50","55" "F0618907C2","6","1","1.2","209","0.450","0.541","55","65","75" "F0412707C2","4","1","1.5","333","0.282","0.340","70","85","95" "F0213312C2","2","1","1.8","530","0.179","0.216","95","115","130" "TBA","1","1","2","669","0.143","0.172","110","130","145" "F1T09704C2","1/0","1","2.2","844","0.113","0.136","125","150","170" "F2T1000400","2/0","1","2.6","1064","0.090","0.108","145","175","195" "F3T10304C2","3/0","1","2.6","1342","0.072","0.087","165","200","225" "F4T1050400","4/0","1","2.9","1692","0.057","0.069","195","230","260" "TBA","250","1","3.3","2000","0.048","0.059","215","255","290" "All dimensions are nominal and subject to normal manufacturing tolerances"