"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","inches","lbs./MFT","lbs./MFT" "890105","1/0","19","0","0.361","80","0.530","326","396" "890106","2/0","19","1","0.405","80","0.572","410","488" "890631","3/0","19","1","0.456","80","0.624","518","603" "890107","4/0","19","1","0.512","80","0.680","653","748" "890632","250","37","1","0.558","95","0.742","771","892" "890108","350","37","1","0.661","95","0.861","1080","1223" "890109","500","37","1","0.789","95","0.966","1543","1707" "890633","750","61","1","0.968","110","1.171","2315","2544" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 60C","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps","Amps" "890105","1/0","0","2.1","844","0.102","0.122","0.044","125","150","170" "890106","2/0","1","2.2","1064","0.081","0.097","0.043","145","175","195" "890631","3/0","1","2.4","1342","0.064","0.078","0.042","165","200","225" "890107","4/0","1","2.7","1692","0.051","0.062","0.041","195","230","260" "890632","250","1","2.9","2000","0.043","0.053","0.041","215","255","290" "890108","350","1","3.4","2800","0.031","0.039","0.040","260","310","350" "890109","500","1","3.8","4000","0.022","0.029","0.039","320","380","430" "890633","750","1","5.9","6000","0.014","0.022","0.038","400","475","535" "All dimensions are nominal and subject to normal manufacturing tolerances"