"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Insulation Thickness","Ground","Jacket Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","mils","No. x AWG","mils","inches","lbs./MFT","lbs./MFT" "955831","14","7","3","30","1 x 14","45","0.409","51","110" "955930","12","7","3","30","1 x 12","45","0.449","81","152" "TBA","14","7","5","30","1 x 14","45","0.482","76","140" "955948","12","7","4","30","1 x 12","45","0.491","101","176" "955955","10","7","3","30","1 x 10","45","0.547","129","224" "TBA","12","7","5","30","1 x 12","60","0.566","121","210" "955963","10","7","4","30","1 x 10","60","0.603","161","273" "666041","10","7","5","30","1 x 10","60","0.657","193","322" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps" "955831","14","3","1.6","2.631","3.170","0.058","20","25" "955930","12","3","1.8","1.662","2.002","0.054","25","30" "TBA","14","5","1.9","2.631","3.170","0.058","16","20" "955948","12","4","2.0","1.662","2.002","0.054","20","24" "955955","10","3","2.2","1.040","1.253","0.050","35","40" "TBA","12","5","2.3","1.662","2.002","0.054","20","24" "955963","10","4","2.4","1.040","1.253","0.050","28","32" "666041","10","5","2.6","1.040","1.253","0.050","28","32" "All dimensions are nominal and subject to normal manufacturing tolerances"