"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Insulation Thickness","Jacket Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","mils","mils","inches","lbs./MFT","lbs./MFT" "576459","18","7","2","15","45","0.174","13","19" "577883","16","7","2","15","45","0.202","21","28" "577884","16","7","3","15","45","0.220","29","39" "586094","18","7","4","15","45","0.303","23","57" "771614","16","7","4","20","45","0.324","40","75" "646279","16","7","4","15","45","0.334","37","76" "577888","18","7","6","15","45","0.365","33","81" "646247","16","7","12","15","45","0.539","101","197" "668251","16","7","16","20","60","0.574","136","237" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps" "576459","18","2","0.7","6.669","8.035","0.036","-","14" "577883","16","2","0.8","4.181","5.037","0.033","-","18" "577884","16","3","0.9","4.181","5.037","0.033","-","18" "586094","18","4","1.2","6.669","8.035","0.036","-","11" "771614","16","4","1.3","4.181","5.037","0.033","-","14" "646279","16","4","1.3","4.181","5.037","0.033","-","14" "577888","18","6","1.5","6.669","8.035","0.036","-","11" "646247","16","12","2.2","4.181","5.037","0.033","-","9" "668251","16","16","2.3","4.181","5.037","0.033","-","9" "All dimensions are nominal and subject to normal manufacturing tolerances"