"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Ground","Jacket Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","No. x AWG","mils","inches","lbs./MFT","lbs./MFT" "TBA","8","19","4","0.143","35","1 x 10","60","0.637","237","346" "TBA","6","19","4","0.179","35","1 x 8","60","0.725","378","506" "TBA","4","19","4","0.226","50","1 x 8","80","0.951","571","799" "643697","2","19","4","0.286","40","1 x 6","80","1.158","909","1243" "TBA","1","37","4","0.333","60","1 x 6","80","1.258","1123","1463" "TBA","1/0","37","4","0.373","60","1 x 6","80","1.355","1395","1767" "TBA","2/0","37","4","0.420","60","1 x 6","80","1.469","1739","2148" "TBA","3/0","37","4","0.471","60","1 x 4","80","1.592","2220","2668" "TBA","4/0","37","4","0.529","60","1 x 4","110","1.793","2764","3361" "TBA","250","61","4","0.575","70","1 x 4","110","1.952","3244","3941" "TBA","350","61","4","0.681","70","1 x 3","110","2.209","4525","5326" "TBA","500","61","4","0.814","70","1 x 2","110","2.531","6436","7368" "TBA","750","91","4","0.998","80","1 x 1","140","3.084","9605","10985" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 60C","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps","Amps" "TBA","8","4","2.5","422","0.653","0.786","0.052","32","40","44" "TBA","6","4","2.9","671","0.411","0.495","0.051","44","52","60" "TBA","4","4","3.8","1068","0.258","0.310","0.048","56","68","76" "643697","2","4","5.8","1698","0.162","0.195","0.045","76","92","104" "TBA","1","4","6.3","2142","0.128","0.154","0.046","88","104","116" "TBA","1/0","4","6.8","2703","0.102","0.122","0.044","100","120","136" "TBA","2/0","4","7.3","3407","0.081","0.097","0.043","116","140","156" "TBA","3/0","4","8.0","4295","0.064","0.078","0.042","132","160","180" "TBA","4/0","4","9.0","5416","0.051","0.062","0.041","156","184","208" "TBA","250","4","9.8","6400","0.043","0.053","0.041","172","204","232" "TBA","350","4","13.3","8960","0.031","0.039","0.040","208","248","280" "TBA","500","4","15.2","12800","0.022","0.029","0.039","256","304","344" "TBA","750","4","18.5","19200","0.014","0.022","0.038","320","380","428" "All dimensions are nominal and subject to normal manufacturing tolerances"