"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Ground","Jacket Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","No. x AWG","mils","inches","lbs./MFT","lbs./MFT" "673535","2","7","4","0.282","45","1 x 6","80","1.078","909","1234" "TBA","1","19","4","0.322","55","1 x 6","80","1.207","1123","1437" "TBA","1/0","19","4","0.361","55","1 x 6","80","1.302","1395","1738" "TBA","4/0","19","4","0.512","55","1 x 4","110","1.727","2764","3320" "TBA","250","37","4","0.558","65","1 x 4","110","1.887","3244","3896" "673550","350","37","4","0.661","65","1 x 3","110","2.187","4530","5552" "TBA","500","37","4","0.789","65","1 x 2","110","2.446","6436","7307" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 60C","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps","Amps" "673535","2","4","5.4","1698","0.162","0.195","0.045","76","92","104" "TBA","1","4","6.0","2142","0.128","0.154","0.046","88","104","116" "TBA","1/0","4","6.5","2703","0.102","0.122","0.044","100","120","136" "TBA","4/0","4","8.6","5416","0.051","0.062","0.041","156","184","208" "TBA","250","4","9.4","6400","0.043","0.053","0.041","172","204","232" "673550","350","4","13.1","8960","0.031","0.039","0.040","208","248","280" "TBA","500","4","14.7","12800","0.022","0.029","0.039","256","304","344" "All dimensions are nominal and subject to normal manufacturing tolerances"