"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Ground","Diameter Over Armor","Jacket Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","No. x AWG","inches","mils","inches","lbs./MFT","lbs./MFT" "550593","8","7","3","0.141","45","3 x 14","0.750","50","0.856","192","407" "890513","6","7","3","0.177","45","3 x 12","0.840","50","0.946","306","547" "890514","4","7","3","0.225","45","3 x 12","0.920","50","1.026","449","714" "890515","2","7","3","0.282","45","3 x 10","1.060","50","1.166","717","1070" "890516","1/0","19","3","0.361","55","3 x 10","1.350","50","1.456","1085","1745" "890517","2/0","19","3","0.405","55","3 x 10","1.470","50","1.576","1342","1935" "890518","3/0","19","3","0.456","55","3 x 8","1.540","60","1.666","1724","2420" "890519","4/0","19","3","0.512","55","3 x 8","1.590","60","1.716","2134","2837" "890520","250","37","3","0.558","65","3 x 8","1.845","60","1.971","2493","3351" "890521","350","37","3","0.661","65","3 x 6","2.040","60","2.166","3520","4535" "890522","500","37","3","0.789","65","3 x 6","2.290","75","2.448","4923","5990" "641426","500","37","3","0.789","65","1 x 4/0","2.430","75","2.588","5337","6449" "646751","600","61","3","0.865","80","3 x 6","2.670","75","2.828","5858","7243" "890523","750","61","3","0.968","80","3 x 4","3.000","75","3.158","7406","9645" "TBA","1000","61","3","1.117","80","3 x 4","3.220","85","3.390","9673","11993" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps" "550593","8","3","6.0","396","0.653","0.786","0.052","50","55" "890513","6","3","6.6","629","0.411","0.495","0.051","65","75" "890514","4","3","7.2","1001","0.258","0.310","0.048","85","95" "890515","2","3","8.2","1592","0.162","0.195","0.045","115","130" "890516","1/0","3","10.2","2534","0.102","0.122","0.044","150","170" "890517","2/0","3","11.0","3194","0.081","0.097","0.043","175","195" "890518","3/0","3","11.7","4027","0.064","0.078","0.042","200","225" "890519","4/0","3","12.0","5078","0.051","0.062","0.041","230","260" "890520","250","3","13.8","6000","0.043","0.053","0.041","255","290" "890521","350","3","15.2","8400","0.031","0.039","0.040","310","350" "890522","500","3","17.1","12000","0.022","0.029","0.039","380","430" "641426","500","3","18.1","12000","0.022","0.029","0.039","380","430" "646751","600","3","19.8","14400","0.018","0.025","0.039","420","475" "890523","750","3","22.1","18000","0.014","0.022","0.038","475","535" "TBA","1000","3","23.7","24000","0.011","0.018","0.037","545","615" "All dimensions are nominal and subject to normal manufacturing tolerances"