"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Ground","Diameter Over Armor","Jacket Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","No. x AWG","inches","mils","inches","lbs./MFT","lbs./MFT" "TBA","8","7","4","0.141","45","1 x 10","0.790","50","0.890","237","504" "TBA","6","7","4","0.177","45","1 x 8","0.920","50","1.020","378","691" "641520","4","7","4","0.225","45","1 x 8","1.020","50","1.120","569","914" "TBA","2","7","4","0.282","45","1 x 6","1.220","50","1.320","907","1358" "TBA","1/0","19","4","0.361","55","1 x 6","1.480","50","1.580","1395","2030" "572421","2/0","19","4","0.405","55","1 x 4","1.540","60","1.660","1790","2444" "550856","4/0","19","4","0.512","55","1 x 4","1.845","60","1.965","2769","3541" "TBA","250","37","4","0.558","65","1 x 4","2.040","60","2.160","3245","4253" "TBA","350","37","4","0.661","65","1 x 3","2.290","75","2.440","4526","5787" "563069","500","37","4","0.789","65","1 x 2","2.670","75","2.820","6443","7756" "TBA","750","61","4","0.968","80","1 x 1","3.220","85","3.390","9607","11602" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps" "TBA","8","4","6.2","422","0.653","0.786","0.052","40","44" "TBA","6","4","7.1","671","0.411","0.495","0.051","52","60" "641520","4","4","7.8","1068","0.258","0.310","0.048","68","76" "TBA","2","4","9.2","1698","0.162","0.195","0.045","92","104" "TBA","1/0","4","11.1","2703","0.102","0.122","0.044","120","136" "572421","2/0","4","11.6","3407","0.081","0.097","0.043","140","156" "550856","4/0","4","13.8","5416","0.051","0.062","0.041","184","208" "TBA","250","4","15.1","6400","0.043","0.053","0.041","204","232" "TBA","350","4","17.1","8960","0.031","0.039","0.040","248","280" "563069","500","4","19.7","12800","0.022","0.029","0.039","304","344" "TBA","750","4","23.7","19200","0.014","0.022","0.038","380","428" "All dimensions are nominal and subject to normal manufacturing tolerances"