"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Ground","Diameter Over Armor","Jacket Thickness","Approx. OD","Copper Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","No. x AWG","inches","mils","inches","lbs./MFT","lbs./MFT" "640853","8","7","3","0.141","45","1 x 10","0.846","55","0.956","186","490" "640881","1","19","3","0.322","55","1 x 6","1.548","65","1.680","864","1639" "640878","1/0","19","3","0.361","55","1 x 6","1.632","65","1.764","1069","1896" "640889","3/0","19","3","0.456","55","1 x 4","1.814","65","1.946","1699","2643" "640898","4/0","19","3","0.512","55","1 x 4","1.943","65","2.075","2109","3205" "640905","350","37","3","0.661","65","1 x 3","2.360","80","2.526","3438","5020" "TBA","500","37","3","0.789","65","1 x 3","2.297","75","2.447","4878","6188" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps" "640853","8","3","6.7","396","0.653","0.786","0.052","50","55" "640881","1","3","11.8","2008","0.128","0.154","0.046","130","145" "640878","1/0","3","12.3","2534","0.102","0.122","0.044","150","170" "640889","3/0","3","13.6","4027","0.064","0.078","0.042","200","225" "640898","4/0","3","14.5","5078","0.051","0.062","0.041","230","260" "640905","350","3","17.7","8400","0.031","0.039","0.040","310","350" "TBA","500","3","17.1","12000","0.022","0.029","0.039","380","430" "All dimensions are nominal and subject to normal manufacturing tolerances"