"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","mils","inches","lbs./MFT","lbs.","inches","inches" TBA,"6","1","7","0.178","125","0.465","80",0.625,"241","209","5.0","2" "958546","2","1","7","0.282","125","0.57","85",0.746,"426","530","5.9","2.5" "953570","2/0","1","19","0.405","125","0.695","85",0.871,"685","1064","6.9","2.5" "611178","500","1","37","0.789","140","1.09","120",1.332,"2084","4000","10.6","4" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90C","Allowable Ampacity In Air 90C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm/MFT","Amps","Amps","Amps" "6","0.403","0.495","0.027","","85","110" "2","0.162","0.204","0.0434","0.186 + j0.023","0.193 + j0.032","","145","190" "2/0","0.081","0.102","0.0387","0.084 + j0.019","0.092 + j0.027","","220","300" "500","0.022","0.030","0.0337","0.012 + j0.014","0.02 + j0.023","","470","695"