"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Ground","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius" "","AWG/Kcmil","","","inches","mils","inches","No. x AWG","mils","inches","lbs./MFT","lbs.","inches" "600429","2","3","7","0.282","90","0.495","1 x 6","80",1.239,"1143","1592","8.6" "600411","1/0","3","19","0.361","90","0.580","1 x 4","80",1.422,"1688","2534","9.9" "600395","4/0","3","19","0.512","90","0.715","1 x 3","110",1.774,"2997","5078","12.4" "679271","350","3","37","0.661","90","0.885","1 x 1","110",2.141,"4578","8400","14.9" "600445","350","3","37","0.661","90","0.885","1 x 2","110",2.156,"4629","8400","15.1" "600387","500","3","37","0.789","90","1.015","1 x 1","110",2.437,"6310","12000","17.1" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.035","0.186 + j0.02","0.196 + j0.029","","135/145","140/154" "1/0","0.102","0.128","0.032","0.11 + j0.017","0.12 + j0.026","","175/190","185/205" "4/0","0.051","0.065","0.030","0.047 + j0.015","0.057 + j0.023","","265/280","285/320" "350","0.031","0.041","0.028","0.023 + j0.013","0.033 + j0.022","","355/380","395/440" "350","0.031","0.041","0.028","0.023 + j0.013","0.033 + j0.022","","355/380","395/440" "500","0.022","0.030","0.027","0.012 + j0.012","0.022 + j0.021","","430/460","485/545"