"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","lbs./MFT","lbs.","inches","inches" "584689","6","1","7","0.174","110",0.430,"137","210","3.4","1.5" "584690","4","1","7","0.225","110",0.481,"215","334","3.8","1.5" "584691","2","1","7","0.283","110",0.537,"313","531","4.3","1.5" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90C","Allowable Ampacity In Air 90C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm/MFT","Amps","Amps","Amps" "6","0.411","0.515","0.042","","85","110" "4","0.258","0.323","0.039","","110","145" "2","0.162","0.203","0.036","","145","190"