"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" "890653","2","1","7","0.282","115","0.545","0.605","55",0.755,"462","530","9.0","2.5" TBA,"1","1","19","0.322","115","0.590","0.650","55",0.780,"477","669","9.3","2.5" "550779","2/0","1","19","0.405","115","0.674","0.734","80",0.914,"758","1064","10.9","3.0" TBA,"3/0","1","19","0.456","115","0.724","0.784","80",0.964,"836","1342","11.5","3.0" "550781","4/0","1","19","0.512","115","0.766","0.826","80",1.006,"1047","1692","12.0","3.0" "568171","250","1","37","0.558","115","0.818","0.878","80",1.058,"1194","2000","12.6","3.0" "890654","350","1","37","0.661","115","0.917","0.977","80",1.157,"1553","2800","13.8","3.5" "550783","500","1","37","0.789","115","1.042","1.102","80",1.282,"2081","4000","15.3","4.0" "551996","750","1","61","0.968","115","1.254","1.314","80",1.494,"2967","6000","17.9","4.5" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.034","0.044","0.57 + j0.514","0.204 + j0.045","1920","145/155","190/215" "1","0.128","0.162","0.031","0.042","0.531 + j0.491","0.162 + j0.042","2044","170/180","225/250" "2/0","0.081","0.102","0.026","0.040","0.473 + j0.447","0.102 + j0.041","2302","220/235","300/330" "3/0","0.064","0.081","0.024","0.039","0.452 + j0.423","0.081 + j0.039","2459","250/270","345/385" "4/0","0.051","0.065","0.021","0.038","0.435 + j0.398","0.065 + j0.038","2633","290/310","400/445" "250","0.043","0.056","0.020","0.037","0.424 + j0.376","0.056 + j0.037","2800","320/345","445/495" "350","0.031","0.041","0.018","0.035","0.404 + j0.338","0.042 + j0.035","3120","385/415","550/615" "500","0.022","0.030","0.015","0.033","0.383 + j0.297","0.031 + j0.033","3516","470/505","695/775" "750","0.014","0.023","0.013","0.032","0.358 + j0.248","0.024 + j0.032","4102","585/630","900/1000"