"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Ground","Diameter Over Armor","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius" "","AWG/Kcmil","","","inches","mils","inches","inches","No. x AWG","inch","mils","inches","lbs./MFT","lbs.","inches" "583246","2","3","7","0.282","115","0.545","0.605","1x6","1.680","65",1.812,"1822","1592","12.6" TBA,"1","3","19","0.322","115","0.590","0.650","1x4","1.769","60",1.889,"1932","2008","13.2" TBA,"1/0","3","19","0.361","115","0.629","0.689","1x4","1.853","60",1.973,"2300","2534","13.8" TBA,"2/0","3","19","0.405","115","0.673","0.733","1x4","1.948","60",2.068,"2645","3194","14.4" TBA,"3/0","3","19","0.456","115","0.724","0.784","1x3","2.058","60",2.178,"3107","4027","15.2" "576651","4/0","3","19","0.512","115","0.766","0.826","1x3","2.155","65",2.287,"3726","5078","16.0" "577531","250","3","37","0.558","115","0.818","0.878","1x2","2.278","80",2.442,"4330","6000","17.0" TBA,"350","3","37","0.661","115","0.937","0.997","1x2","2.518","75",2.668,"5389","8400","18.6" "677577","500","3","37","0.789","115","1.042","1.102","1x1","2.751","80",2.915,"7671","12000","20.4" TBA,"750","3","61","0.968","115","1.254","1.314","1x1/0","3.203","90",3.383,"10099","18000","23.6" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.034","0.040","0.574 + j0.516","0.204 + j0.041","1920","135/145","140/154" "1","0.128","0.162","0.031","0.039","0.535 + j0.492","0.162 + j0.039","2044","155/165","160/180" "1/0","0.102","0.128","0.028","0.037","0.502 + j0.471","0.128 + j0.037","2165","175/190","185/205" "2/0","0.081","0.102","0.026","0.036","0.477 + j0.449","0.102 + j0.036","2302","200/220","215/240" "3/0","0.064","0.081","0.024","0.035","0.456 + j0.424","0.081 + j0.035","2459","230/250","250/280" "4/0","0.051","0.065","0.021","0.034","0.439 + j0.399","0.065 + j0.034","2633","265/280","285/320" "250","0.043","0.056","0.020","0.033","0.428 + j0.376","0.056 + j0.033","2800","290/315","320/355" "350","0.031","0.041","0.018","0.032","0.406 + j0.338","0.041 + j0.032","3120","355/380","395/440" "500","0.022","0.030","0.015","0.030","0.385 + j0.297","0.03 + j0.03","3516","430/460","485/545" "750","0.014","0.023","0.013","0.029","0.36 + j0.248","0.023 + j0.029","4102","530/570","615/685"