"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" TBA,"2","1","7","0.282","140","0.600","0.660","55",0.790,"439","530","9.4","2.5" TBA,"1","1","19","0.322","140","0.640","0.700","80",0.880,"554","669","10.5","2.5" TBA,"1/0","1","19","0.361","140","0.679","0.739","80",0.919,"639","844","11.0","3.0" TBA,"2/0","1","19","0.405","140","0.723","0.783","80",0.963,"746","1064","11.5","3.0" TBA,"3/0","1","19","0.456","140","0.774","0.834","80",1.014,"878","1342","12.1","3.0" "584285","4/0","1","19","0.512","140","0.816","0.876","80",1.056,"1086","1692","12.6","3.0" TBA,"250","1","37","0.558","140","0.884","0.944","80",1.124,"1189","2000","13.4","3.5" TBA,"350","1","37","0.661","140","0.987","1.047","80",1.227,"1550","2800","14.7","3.5" "555204","500","1","37","0.789","140","1.092","1.152","80",1.332,"2127","4000","15.9","4.0" "568211","750","1","61","0.968","140","1.304","1.364","80",1.544,"3019","6000","18.5","4.5" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.039","0.045","0.573 + j0.49","0.204 + j0.046","2075","155/165","195/215" "1","0.128","0.162","0.035","0.045","0.532 + j0.467","0.162 + j0.045","2199","175/185","225/250" "1/0","0.102","0.128","0.032","0.043","0.499 + j0.447","0.128 + j0.043","2320","200/215","260/290" "2/0","0.081","0.102","0.030","0.042","0.473 + j0.426","0.102 + j0.042","2456","230/245","300/335" "3/0","0.064","0.081","0.027","0.040","0.451 + j0.403","0.081 + j0.04","2614","260/275","345/385" "4/0","0.051","0.065","0.025","0.039","0.433 + j0.38","0.065 + j0.039","2788","295/315","400/445" "250","0.043","0.056","0.024","0.038","0.422 + j0.359","0.057 + j0.038","2955","325/345","445/495" "350","0.031","0.041","0.020","0.036","0.4 + j0.323","0.042 + j0.036","3274","390/415","550/610" "500","0.022","0.030","0.018","0.034","0.378 + j0.284","0.031 + j0.034","3671","465/500","685/765" "750","0.014","0.023","0.015","0.032","0.353 + j0.238","0.024 + j0.032","4257","565/610","885/990"