"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" TBA,"2","1","7","0.282","175","0.670","0.730","80",0.910,"532","530","10.9","2.5" TBA,"1","1","19","0.322","175","0.710","0.770","80",0.950,"608","669","11.4","3.0" TBA,"1/0","1","19","0.361","175","0.749","0.809","80",0.989,"696","844","11.8","3.0" TBA,"2/0","1","19","0.405","175","0.793","0.853","80",1.033,"805","1064","12.3","3.0" TBA,"3/0","1","19","0.456","175","0.844","0.904","80",1.084,"941","1342","13.0","3.0" TBA,"4/0","1","19","0.512","175","0.900","0.960","80",1.140,"1105","1692","13.6","3.5" TBA,"250","1","37","0.558","175","0.954","1.014","80",1.194,"1258","2000","14.3","3.5" "678579","350","1","37","0.661","175","1.037","1.097","80",1.277,"1670","2800","15.3","3.5" TBA,"350","1","37","0.661","175","1.057","1.117","80",1.297,"1623","2800","15.5","4.0" "586466","500","1","37","0.789","175","1.162","1.222","80",1.402,"2208","4000","16.8","4.0" TBA,"600","1","61","0.865","175","1.271","1.331","80",1.511,"2518","4800","18.1","4.5" TBA,"750","1","61","0.968","175","1.374","1.434","80",1.614,"3040","6000","19.3","4.5" TBA,"1000","1","61","1.117","175","1.523","1.583","110",1.823,"4001","8000","21.8","5.0" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.044","0.049","0.575 + j0.458","0.204 + j0.05","2292","155/165","195/215" "1","0.128","0.162","0.041","0.047","0.533 + j0.437","0.162 + j0.047","2416","175/185","225/250" "1/0","0.102","0.128","0.037","0.045","0.499 + j0.418","0.128 + j0.045","2537","200/215","260/290" "2/0","0.081","0.102","0.035","0.043","0.472 + j0.399","0.102 + j0.043","2673","230/245","300/335" "3/0","0.064","0.081","0.032","0.042","0.449 + j0.377","0.082 + j0.042","2831","260/275","345/385" "4/0","0.051","0.065","0.029","0.040","0.43 + j0.356","0.066 + j0.04","3005","295/315","400/445" "250","0.043","0.056","0.027","0.039","0.417 + j0.336","0.057 + j0.039","3172","325/345","445/495" "350","0.031","0.041","0.024","0.037","0.394 + j0.303","0.042 + j0.037","3491","390/415","550/610" "350","0.031","0.041","0.024","0.037","0.394 + j0.303","0.042 + j0.037","3491","390/415","550/610" "500","0.022","0.030","0.021","0.035","0.372 + j0.268","0.031 + j0.035","3888","465/500","685/765" "600","0.018","0.026","0.020","0.034","0.36 + j0.247","0.027 + j0.034","4154","505/544","765/855" "750","0.014","0.023","0.018","0.033","0.346 + j0.225","0.024 + j0.033","4473","565/610","885/990" "1000","0.011","0.019","0.016","0.033","0.327 + j0.198","0.02 + j0.033","4935","640/690","1060/1185"