"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" TBA,"2","1","7","0.268","220","0.746","0.806","80",0.986,"455","398","11.8","3.0" TBA,"1","1","19","0.298","220","0.776","0.836","80",1.016,"489","502","12.1","3.0" TBA,"1/0","1","19","0.336","220","0.814","0.874","80",1.054,"534","633","12.6","3.0" TBA,"2/0","1","19","0.376","220","0.854","0.914","80",1.094,"585","798","13.1","3.0" TBA,"3/0","1","19","0.422","220","0.900","0.960","80",1.140,"644","1006","13.6","3.5" TBA,"4/0","1","19","0.474","220","0.952","1.012","80",1.192,"718","1269","14.3","3.5" "589002","250","1","22","0.520","220","1.006","1.066","80",1.266,"930","1500","15.1","3.5" TBA,"350","1","35","0.615","220","1.101","1.161","80",1.341,"944","2100","16.0","4.0" "640814","500","1","34","0.735","220","1.244","1.304","80",1.504,"1341","3000","18.0","4.5" TBA,"600","1","58","0.812","220","1.308","1.368","80",1.548,"1315","3600","18.5","4.5" "589001","750","1","58","0.908","220","1.426","1.486","80",1.746,"1821","4500","20.9","5.0" "585564","1000","1","61","1.060","220","1.568","1.628","110",1.888,"2161","6000","22.6","5.5" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.267","0.336","0.053","0.052","0.707 + j0.426","0.336 + j0.051","2528","120/130","150/170" "1","0.211","0.266","0.049","0.050","0.636 + j0.41","0.266 + j0.048","2621","135/145","175/195" "1/0","0.168","0.211","0.046","0.048","0.58 + j0.393","0.211 + j0.047","2738","155/165","200/225" "2/0","0.133","0.167","0.042","0.046","0.534 + j0.376","0.168 + j0.045","2862","175/190","235/260" "3/0","0.105","0.133","0.039","0.044","0.498 + j0.358","0.134 + j0.043","3005","200/215","270/300" "4/0","0.084","0.105","0.036","0.043","0.466 + j0.339","0.106 + j0.041","3166","230/245","310/350" "250","0.071","0.090","0.034","0.042","0.447 + j0.321","0.091 + j0.04","3333","250/270","345/385" "350","0.050","0.065","0.030","0.040","0.415 + j0.292","0.066 + j0.038","3628","305/330","430/480" "500","0.035","0.046","0.026","0.037","0.384 + j0.26","0.047 + j0.036","3999","370/400","535/600" "600","0.029","0.039","0.024","0.037","0.369 + j0.239","0.04 + j0.034","4269","404/436","601/672" "750","0.024","0.033","0.022","0.035","0.353 + j0.22","0.034 + j0.034","4566","455/490","700/780" "1000","0.018","0.026","0.020","0.035","0.331 + j0.194","0.027 + j0.033","5037","525/565","840/940"