"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" TBA,"2","1","7","0.268","220","0.746","0.806","80",0.986,"598","530","11.8","3.0" TBA,"1","1","19","0.298","220","0.776","0.836","80",1.016,"670","669","12.1","3.0" "647203","1/0","1","19","0.336","220","0.814","0.874","80",1.054,"800","844","12.6","3.0" TBA,"2/0","1","19","0.376","220","0.854","0.914","80",1.094,"871","1064","13.1","3.0" TBA,"3/0","1","19","0.422","220","0.900","0.960","80",1.140,"1004","1342","13.6","3.5" "640921","4/0","1","19","0.474","220","0.953","1.013","80",1.193,"1012","1692","14.3","3.5" TBA,"250","1","37","0.520","220","1.006","1.066","80",1.246,"1329","2000","14.9","3.5" "647207","350","1","35","0.615","220","1.102","1.162","80",1.342,"1747","2800","16.1","4.0" "553998","500","1","35","0.735","220","1.230","1.290","80",1.470,"2301","4000","17.6","4.5" TBA,"600","1","61","0.812","220","1.308","1.368","80",1.548,"2600","4800","18.5","4.5" "561603","750","1","61","0.908","220","1.404","1.495","80",1.735,"3331","6000","20.8","5.0" TBA,"1000","1","61","1.060","220","1.556","1.616","110",1.856,"4101","8000","22.2","5.5" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.053","0.052","0.575 + j0.426","0.204 + j0.051","2528","155/165","195/215" "1","0.128","0.162","0.049","0.050","0.532 + j0.410","0.162 + j0.048","2621","175/185","225/250" "1/0","0.102","0.128","0.046","0.048","0.497 + j0.393","0.128 + j0.047","2738","200/215","260/290" "2/0","0.081","0.102","0.042","0.046","0.469 + j0.376","0.103 + j0.045","2862","230/245","300/335" "3/0","0.064","0.081","0.039","0.044","0.446 + j0.358","0.082 + j0.043","3005","260/275","345/385" "4/0","0.051","0.065","0.036","0.043","0.426 + j0.339","0.066 + j0.041","3166","295/315","400/445" "250","0.043","0.056","0.034","0.042","0.413 + j0.321","0.057 + j0.040","3333","325/345","445/495" "350","0.031","0.041","0.030","0.040","0.391 + j0.292","0.042 + j0.038","3628","390/415","550/610" "500","0.022","0.030","0.026","0.037","0.368 + j0.260","0.031 + j0.036","3999","465/500","685/765" "600","0.018","0.026","0.024","0.037","0.356 + j0.239","0.027 + j0.034","4269","505/544","765/855" "750","0.014","0.023","0.022","0.035","0.343 + j0.220","0.024 + j0.034","4566","565/610","885/990" "1000","0.011","0.019","0.020","0.035","0.324 + j0.194","0.02 + j0.033","5037","640/690","1060/1185"