"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" TBA,"1/0","1","19","0.361","420","1.239","1.299","80",1.479,"1207","844","17.7","4.5" TBA,"2/0","1","19","0.405","420","1.283","1.343","80",1.523,"1333","1064","18.2","4.5" TBA,"3/0","1","19","0.456","420","1.334","1.394","80",1.574,"1488","1342","18.8","4.5" TBA,"4/0","1","19","0.512","420","1.390","1.450","80",1.630,"1676","1692","19.5","4.5" TBA,"250","1","37","0.558","420","1.444","1.504","110",1.744,"1950","2000","20.9","5.0" TBA,"250","1","37","0.558","420","1.444","1.504","110",1.744,"1950","2000","20.9","5.0" TBA,"350","1","37","0.661","420","1.547","1.607","110",1.847,"2364","2800","22.1","5.5" "679731","500","1","37","0.789","420","1.652","1.712","110",1.952,"2995","4000","23.4","5.5" TBA,"750","1","61","0.968","420","1.864","1.924","110",2.164,"3926","6000","25.9","6.0" TBA,"1000","1","61","1.117","420","2.013","2.073","110",2.313,"4851","8000","27.7" TBA,"1250","1","91","1.250","420","2.150","2.210","110",2.450,"5765","10000","29.4" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "1/0","0.102","0.128","0.064","0.054","0.465 + j0.274","0.129 + j0.054","4055","200/215","260/290" "2/0","0.081","0.102","0.060","0.052","0.434 + j0.263","0.103 + j0.052","4192","230/245","300/330" "3/0","0.064","0.081","0.056","0.050","0.408 + j0.25","0.082 + j0.05","4350","260/275","345/380" "4/0","0.051","0.065","0.052","0.048","0.387 + j0.237","0.066 + j0.049","4523","295/315","395/445" "250","0.043","0.056","0.049","0.048","0.372 + j0.227","0.057 + j0.048","4690","325/345","440/490" "250","0.043","0.056","0.049","0.048","0.372 + j0.227","0.057 + j0.048","4690","325/345","440/490" "350","0.031","0.041","0.044","0.045","0.347 + j0.207","0.042 + j0.045","5009","390/415","545/605" "500","0.022","0.030","0.039","0.043","0.324 + j0.187","0.031 + j0.043","5406","465/500","680/755" "750","0.014","0.023","0.034","0.040","0.3 + j0.161","0.024 + j0.04","5992","565/610","870/970" "1000","0.011","0.019","0.030","0.038","0.283 + j0.145","0.02 + j0.038","6453","640/690","1040/1160" "1250","0.009","0.018","0.028","0.037","0.271 - j0.124","0.019 - j0.219","6878","715/770","1185/1320"