"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Ground","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius" "","AWG/Kcmil","","","inches","mils","inches","inches","No. x AWG","mils","inches","lbs./MFT","lbs.","inches" "669151","4/0","3","19","0.512","420","1.390","1.450","3x6","135",3.665,"6871","5078","25.6" "669160","350","3","37","0.661","420","1.527","1.587","3x6","135",3.961,"8779","8400","27.7" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "4/0","0.051","0.065","0.052","0.046","0.388 + j0.237","0.066 + j0.046","4523","285/305","325/360" "350","0.031","0.041","0.044","0.042","0.348 + j0.207","0.042 + j0.042","5009","375/400","435/490"