SPEC 45307

CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type MC Power Cable 600Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:Aluminum Interlocked Armor (AIA)
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE {UL} 4/C (XX AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGinchmilinchlb/1000ftlb/1000ft
    TBA8470.141451 x 100.771500.871237461
    5744606470.177451 x 80.865500.965378650
    TBA4470.225451 x 80.974501.074571872
    5807302470.282451 x 61.113501.2139091279
    TBA14190.322551 x 61.257501.35711231552
    8902291/04190.361551 x 61.352501.45213991907
    TBA2/04190.405551 x 61.458501.55817392250
    TBA3/04190.456551 x 41.682601.80222202858
    5626054/04190.512551 x 41.785601.90527693534
    5579592504370.558651 x 41.940602.06032484153
    5514523504370.661651 x 32.179602.29945305709
    TBA3504370.661651 x 2/02.226602.34645255565
    6054105004370.789651 x 22.484752.63464437854
    5634076004610.865801 x 22.765752.91576919303
    6729896004610.865801 x 4/02.798802.96481459698
    TBA7504610.968801 x 13.042853.212960511336
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftAmpAmp
    TBA846.14220.6530.7860.0330.0524044
    574460646.86710.4110.4950.0270.0515260
    TBA447.510680.2580.3100.0220.0486876
    580730248.516980.1620.1950.0180.04592104
    TBA149.521420.1280.1540.0190.046104116
    8902291/0410.227030.1020.1220.0170.044120136
    TBA2/0410.934070.0810.0970.0160.043140156
    TBA3/0412.642950.0640.0780.0140.042160180
    5626054/0413.354160.0510.0620.0130.041184208
    557959250414.464000.0430.0530.0140.041204232
    551452350416.189600.0310.0390.0120.040248280
    TBA350416.489600.0310.0390.0120.040248280
    605410500418.4128000.0220.0290.0100.039304344
    563407600420.4153600.0180.0250.0110.039336380
    672989600420.7153600.0180.0250.0110.039336380
    TBA750422.5192000.0140.0220.0100.038380428
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.006

    Updated On: Jan. 24, 2024, 6:15 p.m. UTC