SPEC 42054

MG 550°C 300V UL 5390

High Temperature Lead Wire, Temp Rating 550°C

...

Construction:

  1. Conductor:flexible stranded 27% nickel plated, annealed copper
  2. Insulation:Mica fiberglass composite
  3. Jacket:A fiberglass braid jacket is applied over the insulation, then treated with a high-temperature saturant. Natural color is tan.

Applications and Features:

Internal wiring. Approved for use up to 550°C. Excellent thermal and flame resistance, good chemical resistance, and produces minimal smoke when exposed to flames. Colors available upon request.

Specifications:

  • UL AWM Appliance wire approvals as listed in Table 1
  • CSA AWM I A/B FT1
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsInsul. ThicknessBraidApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/Kcmilstrandmilmilinchlb/1000ft°CStyle/Type
    C2243C247/.0082770.08165505390
    C2223C227/.01002770.08875505390
    C2203C2010/.01002770.09285505390
    C2183C1816/.01002770.105125505390
    C2163C1626/.01002770.120165505390
    C2143C1441/.01002770.130225505390
    C2123C1265/.01002770.150315505390
    C2103C10105/.01003570.210525505390
    C2083C8133/.011135120.260785505390
    C2063C6133/.014235120.3001165505390
    C2043C4133/.017735120.3501755505390

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Dimensions and weights for other cable configurations are available upon request.

    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. StrandsInsul. ThicknessBraidApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/Kcmilstrandmmmmmmkg/km°CStyle/Type
    C2243C247/.0080.690.182.0695505390
    C2223C227/.01000.690.182.24105505390
    C2203C2010/.01000.690.182.34125505390
    C2183C1816/.01000.690.182.67185505390
    C2163C1626/.01000.690.183.05245505390
    C2143C1441/.01000.690.183.30335505390
    C2123C1265/.01000.690.183.81465505390
    C2103C10105/.01000.890.185.33775505390
    C2083C8133/.01110.890.306.601165505390
    C2063C6133/.01420.890.307.621735505390
    C2043C4133/.01770.890.308.892605505390

    Revision: 1.0.00M