SPEC 42066

SRG-K POWER CABLES

Silicone Rubber Glass Braid Conductors with an Overall Aramid Fiber Jacket, Temp Rating 200°C, 600V

...

Construction:

  1. Conductor:Stranded tinned, annealed copper per ASTM B33
  2. Insulation:Silicone Rubber with a fiberglass braid over the insulation
  3. Cabling:Conductors are cabled with a left hand lay and bound with a polyester tape
  4. Jacket:K-Fiber braid, treated with a high temperature saturant, covers the core

Applications and Features:

Used for equipment wiring, as well as signal and control circuits. Ideal in locations where high temperature or hazardous conditions exist that require heat resistance at 600 volts.
K Fiber Jacket provides improved mechanical strength and abrasion resistance. Good chemical strength. Excellent electrical properties. Passes IEEE 383 70,000 BTU/Hr Flame test while maintaining circuit integrity.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • IEEE 383 Flame Test (70,000 btu)
  • RoHS-3 Complies with European Directive 2015/863
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/KcmilNo.milinchlb/1000ft°CStyle/Type
    C5150082600.620180200Non-UL
    C5150583600.660265200Non-UL
    C5151084600.750350200Non-UL
    C5152562600.675250200Non-UL
    C5153063600.730355200Non-UL
    C5153564600.820480200Non-UL
    C5155042600.840385200Non-UL
    C5155543600.910625200Non-UL
    C5156044601.020825200Non-UL
    C5157522600.980630200Non-UL
    C5158023601.050925200Non-UL
    C5158524601.1801225200Non-UL

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberInsul. ThicknessApprox. ODApprox. WeightTemp. RatingStandard (UL or other)
    AWG/KcmilNo.mmmmkg/km°CStyle/Type
    C51500821.5215.75268200Non-UL
    C51505831.5216.76394200Non-UL
    C51510841.5219.05521200Non-UL
    C51525621.5217.15372200Non-UL
    C51530631.5218.54528200Non-UL
    C51535641.5220.83714200Non-UL
    C51550421.5221.34573200Non-UL
    C51555431.5223.11930200Non-UL
    C51560441.5225.911228200Non-UL
    C51575221.5224.89938200Non-UL
    C51580231.5226.671377200Non-UL
    C51585241.5229.971823200Non-UL

    Revision: 1.0.00M