SPEC 44140

3/C CU 2000V EPDM/CPE Type G-GC Industrial Grade Cable 90°C

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red
  4. Ground Check:One insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  5. Ground Conductors:Two insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  6. Fillers:Paper fillers applied as needed to round the cable core
  7. Tape:Reinforcing tape applied over the cabled core for improved mechanical integrity and ease of stripping
  8. Reinforcement Binder:Reinforcing twine applied over the tapped core
  9. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Applications and Features:

2 AWG 3/C TYPE G-GC PORTABLE POWER CABLE 90°C WET OR DRY 2000V OIL AND SUN RES (UL) P-136-35-MSHA AIWTM c(UL) FT1/FT5 (-40°C)

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    Southwire Type G-GC cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required per Article NEC 400. Suitable for continuous submersion in water – ideal for submers- ible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as perminant building wiring. Meets FT-5 Flame Test. cUL Listed.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundGround StrandsGround Check SizeGround Check StrandsApprox. ODApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGNo.AWGNo.inchlb/1000ft
    5605378710.148600.32 x 10104101040.95610
    5581686650.184600.332 x 10104101041.03730
    55816941120.235600.392 x 841101041.11970
    55817021680.315600.472 x 752101041.311340
    57009812240.362800.552 x 62738711.51770
    5581651/02590.385800.582 x 51338711.582070
    5581662/03240.42800.612 x 41338711.652450
    5600653/04180.47800.662 x 31338711.762970
    5581674/05320.535800.732 x 22598711.933630
    5702392506080.605950.832 x 22598712.294460
    5592813508550.67950.892 x 1/02598712.435810
    57024350012210.858951.082 x 2/03248712.897970

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusDC ResistanceAC Resistance @ 90°CInductive ReactanceAllowable Ampacity In Air 60°CAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°C
    AWG/KcmilinchΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    560537860.65300.8160.038485765
    558168660.41900.5240.035637787
    558169470.26300.3290.03384101114
    558170280.16600.2080.031112133152
    570098190.13100.1640.031131156177
    5581651/090.10500.1310.031151181205
    5581662/0100.08340.1040.030174208237
    5600653/0110.06620.0830.030201241274
    5581674/0120.05250.0660.029232277316
    570239250140.04480.0560.029259310352
    559281350150.03200.0400.028318381433
    570243500170.02240.0280.027392470536