SPEC 45041

Machine Tray Control Cable Cu 600/1000V PVC THHN TPE Jacket

Type TC-ER Machine Tray Control Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Gray Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s machine control tray cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emer- gency overload, and 250°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s machine tray cable is ideal for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind ener- gy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables Type THHN
  • UL 758 Standard for Appliance Wiring Material Style 2463 (80C, 600V)
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power cables rated 2000 volts or less for the distribution of electrical energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Sample Print Legend:

    Southwire XXAWG (XXmm2) XX/C PVC/Nylon Type TC-ER EXXXXX (UL) 600V 90°C Dry 75C Wet Sun Res Oil Res I/II DIR BUR - 40°C OR MTW Flexing OR DP-1 OR WTTC 1000V OR AWM 20886 105°C 1000V OR c(UL) CIC/TC FT4 -- LLXXXXXX CSA AWM I/II A/B 105°C 1000V -40°C FT4 -- CE RoHS -2 Made in USA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilConductorsNo.milmilinchlb/1000ft
    6770711821620450.26635
    5815111831620450.28147
    5826421841620450.30659
    5826441851620450.33268
    5815131871620450.35885
    5826451891620450.411107
    58264618121620450.456135
    58264718181620450.554207
    64626218191620450.563212
    58151418251620600.635245
    6770721622620500.29445
    5815151632620500.31160
    5826481642620500.33976
    5826491652620500.37089
    5815161672620500.400113
    5826511692620500.462144
    58265216122620500.509199
    58265316182620650.623280
    64626316192620650.663310
    58151716252620650.717348
    6770731424120500.32459
    5815191434120500.34282
    5826541444120500.375106
    5826551454120500.411125
    5815211474120500.445160
    5826561494120500.516205
    58265714124120650.600282
    58265814184120650.697402
    58152214254120650.806565
    6770741226520500.36280
    6771881236520500.389108
    5826591246520500.420147
    5826601256520500.462176
    5826611276520500.502227
    67707510210525500.430119
    67718910310525500.462160
    58152310410525500.502206
    58266210510525500.530255
    58266310710525650.608364
    6771908316836680.626296
    6433678416836600.680329
    6771916327336700.725441
    6433696427336600.760466
    6771924342746800.898649
    6433714442746800.969738
    67719323651461001.070988
    6433732465146801.1621130

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    ConductorsAWG/KcmilinchAmpAmpAmp
    6770711821.10777
    5815111831.12777
    5826421841.22777
    5826441851.33777
    5815131871.43777
    5826451891.64777
    58264618121.82777
    58264718182.22777
    64626218192.25777
    58151418252.54777
    6770721621.18101010
    5815151631.24101010
    5826481641.36101010
    5826491651.48101010
    5815161671.60101010
    5826511691.85101010
    58265216122.04999
    58265316182.49999
    64626316192.65999
    58151716252.87888
    6770731421.29151515
    5815191431.37151515
    5826541441.50151515
    5826551451.64151515
    5815211471.78141414
    5826561492.06141414
    58265714122.40101010
    58265814182.79101010
    58152214253.22999
    6770741221.45202020
    6771881231.56202020
    5826591241.68202020
    5826601251.85202020
    5826611272.01171717
    6770751021.72282828
    6771891031.85282828
    5815231042.01282828
    5826621052.01282828
    5826631072.43242424
    677190832.5404040
    643367842.72324044
    677191633.04555555
    643369643.04404040
    677192433.59686868
    643371443.88686868
    677193235.35929292
    643373245.81929292

    Notes: