SPEC 45058

Multi-Conductor CU 600V PVC Type TC SDN Flexible Control Cable

Type TC-SDN® Control Cable 600 Volt Flexible Strand Bare Copper Conductors, Polyvinyl Chloride (PVC) insulation with nylon sheath THHN/THWN, Black Neoprene Jacket, Oil and Sunlight Resistant 90°C Dry 75°C Wet

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon sheath THHN/THWN. Color code Method 1 Table 2 with no white or green.
  3. Fillers:Polypropylene or paper to form round core
  4. Binder:Two mil mylar tape helically applied over core
  5. Jacket:Black heavy duty sunlight and oil resistant Neoprene

Applications and Features:

Southwire SDN (Small Diameter Neoprene) flexible control tray cables 600 Volt are suited for use in industrial power or control circuits where small diameter, flame retardant cables are desired. These cables are suitable for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Southwire SDN cables listed ast THHN/THWN are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC Article 501 and 502. Southwire SDN flexible control cable is CSA listed Type TC and as Control and Instrumentation Cable Type (CIC)

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B172 Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper Conductors
  • UL 66 Fixture Wire Type TFFN
  • UL 83 Thermoplastic Insulated Wires and Cables Type THHN
  • UL 1277 Electrical Power and Control Tray Cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE® SDN 12 AWG (3.31mm2) 4/C TC 90C DRY 75C WET SUN RES 600V DIR BUR E75755 (UL) --- CSA CIC/TC 90C DRY 75C WET PVC/N (-40C) 600V SR OIL RES FT4
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilConductorsinchmilmilinchlb/1000ft
    5699251830.04420450.28347
    5699261850.04420450.33470
    5699271860.04420450.36077
    5699281880.04420450.38794
    57134118100.04420500.417116
    56992918120.04420500.442131
    56994318140.04420500.486150
    57134218160.04420500.511170
    56994418190.04420650.515200
    57138918240.04420700.651258
    56993018370.04420700.740372
    5699121620.05820450.30251
    5713401630.05820450.31362
    5699141640.05820450.34175
    5699151650.05820450.37292
    5699161660.05820450.402102
    5699171670.05820450.402113
    56991016100.05820450.454150
    5699181680.05820600.457136
    5700891690.05820600.487151
    56991916120.05820600.524191
    57009016140.05820600.569218
    56992016160.05820600.598244
    56992216190.05820600.632280
    56991116240.05820650.690346
    56992316300.05820700.745425
    56992416370.05820900.876548
    5699311430.07420450.34480
    5699321440.07420450.37799
    5699331450.07420450.413121
    5699341460.07420450.447138
    5700911480.07420650.518192
    56993514100.07420700.595235
    57009214120.07420650.602267
    56993614160.07420650.678341
    57009414240.07420700.784489
    57009514370.07420900.979754
    5699371230.09220450.383115
    5699381240.09220450.422140
    5699401250.09220450.464176
    5699411260.09220450.504203
    5699421280.09220850.620297
    57131312120.09220650.688394

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusDC Resistance @ 25°CAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    ConductorsAWG/KcmilinchΩ/1000ftAmpAmpAmp
    5699251831.136.66777
    5699261851.346.66777
    5699271861.446.66777
    5699281881.556.66777
    57134118101.676.66777
    56992918121.776.66777
    56994318141.946.66777
    57134218162.046.66777
    56994418192.066.66777
    57138918242.606.66666
    56993018372.966.66666
    5699121621.214.18101010
    5713401631.254.18101010
    5699141641.364.18101010
    5699151651.494.18101010
    5699161661.614.18101010
    5699171671.614.1891010
    56991016101.824.18679
    5699181681.834.1891010
    5700891691.954.1891010
    56991916122.104.18679
    57009016142.284.18679
    56992016162.394.18679
    56992216192.534.18679
    56991116242.764.18678
    56992316302.984.18678
    56992416373.504.18678
    5699311431.382.63151515
    5699321441.512.63151515
    5699331451.652.63141515
    5699341461.792.63141515
    5700911482.072.63121515
    56993514102.382.6391112
    57009214122.412.6391112
    56993614162.712.6391112
    57009414243.142.638911
    57009514373.922.63789
    5699371231.531.65202020
    5699381241.691.65162020
    5699401251.861.65162020
    5699411262.021.65162020
    5699421282.481.65141720
    57131312122.751.65101215