SPEC 45059

Multi-Conductor CU 600V EPR XHHW-2 CPE Control Cable Color Method 1 Table 1

Type TC-ER Control Cable 600Volt Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2 Chlorinated Polyethylene (CPE) Jacket, Control Cable Conductor Identification Method 1 Table 1

...

Construction:

  1. Conductor:7 strands class B compressed tinned copper per ASTM B33 and ASTM B8
  2. Insulation:Ethylene Propylene Rubber (EPR) XHHW-2, 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Chlorinated Polyethylene (CPE) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1581 Electrical Wires, Cables and Flexible Cords
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power cables rated 2000 volts or less for the distribution of electrical energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE EXXXXX #P# (UL) [#AWG Or #kcmil] CU XHHW-2 EPR/CPE 600V Type TC-ER For CT USE SUN. RES. For DIRECT BURIAL FT4 YEAR (NESC) [SEQUENTIAL FEET MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilConductorsinchmilmilinchlb/1000ftlb/1000ft
    TBA1420.07030450.3492669
    5994571430.07030450.3703888
    5994581440.07030450.40351109
    5994591450.07030450.44064132
    5954791470.07030450.47990171
    5994601490.07030600.588115237
    59946114120.07030600.659154303
    TBA14150.07030600.730192371
    59547514190.07030600.768243444
    TBA14250.07030800.937320619
    TBA14300.07030800.991384718
    TBA14370.07030801.067474859
    5956351220.08730450.3844191
    5954721230.08730450.40861118
    5956361240.08730450.44581149
    5921111250.08730450.487102181
    TBA1270.08730450.532143237
    5969191290.08730600.651183325
    59547712120.08730600.732244419
    TBA12150.08730600.813305516
    TBA12190.08730800.896387657
    TBA12250.08730801.043509859
    TBA12300.08730801.1046111002
    TBA12370.08730801.1917531205
    5956321020.11130450.43165125
    5955561030.11130450.45997166
    5956331040.11130600.556130223
    TBA1050.11130600.581162274
    TBA1070.11130600.632227359
    TBA1090.11130600.736291462
    TBA10120.11130600.830389600
    TBA10150.11130800.964486778
    TBA10190.11130801.014615940
    TBA10250.11130801.1848101233
    TBA10300.11130801.2549711446
    TBA10370.11130801.35511981747

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 90°CAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    ConductorsAWG/KcmilinchΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA1421.42.6303.288151515
    5994571431.52.6303.288151515
    5994581441.62.6303.288141515
    5994591451.82.6303.288141515
    5954791471.92.6303.288121515
    5994601492.42.6303.288121515
    59946114122.62.6303.28891112
    TBA14152.92.6303.28891112
    59547514193.12.6303.28891112
    TBA14253.72.6303.2888911
    TBA14304.02.6303.2888911
    TBA14375.32.6303.2887810
    5956351221.51.6602.075202020
    5954721231.61.6602.075202020
    5956361241.81.6602.075162020
    5921111251.91.6602.075162020
    TBA1272.11.6602.075141720
    5969191292.61.6602.075141720
    59547712122.91.6602.075101215
    TBA12153.31.6602.075101215
    TBA12193.61.6602.075101215
    TBA12255.21.6602.07591113
    TBA12305.51.6602.07591113
    TBA12376.01.6602.07581012
    5956321021.71.0401.300303030
    5955561031.81.0401.300303030
    5956331042.01.0401.300242830
    TBA1052.31.0401.300242830
    TBA1072.51.0401.300212428
    TBA1092.91.0401.300212428
    TBA10123.31.0401.300151720
    TBA10153.91.0401.300151720
    TBA10195.11.0401.300151720
    TBA10255.91.0401.300131518
    TBA10306.31.0401.300131518
    TBA10376.81.0401.300121416