SPEC 45411

2000 Volt Copper Type PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Copper Conductor XLPE Insulation. Sizes 12 AWG through 1000 Kcmil. Heat, Moisture, Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 4703 Standard for Photovoltaic Wire
  • Sample Print Legend:

    SOUTHWIRE EXXXXXX {UL} XX AWG (XX.X{mm2}) CU 2000V 90{D}C WET OR DRY () --- RoHS [SEQUENTIAL FEET MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilConductorsNo.inchmilinchlb/1000ftlb/1000ft
    TBA4/01190.5101050.705653749
    5782983/01190.4541050.664518604
    5690442/01190.4041050.614411489
    5690431/01190.3601050.57326396
    TBA10001611.1171351.40230883336
    TBA7501610.9681351.26323162534
    TBA6001610.8661351.1218532051
    5783245001370.7891201.0315441706
    TBA3501370.6611200.88610811219
    TBA2501370.5581200.783772891
    59795812170.087750.2432040
    57996210170.113750.2633253
    5690378170.139850.3135180
    5690396170.174850.34981113
    5690404170.221850.395129167
    5690412170.277850.456205251
    56904211190.3211050.531258323

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 90°CAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    ConductorsAWG/KcmilinchΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA4/015.50.0510.064195230260
    5782983/015.10.0640.081165200225
    5690442/014.70.0810.102145175195
    5690431/014.30.1020.128125150170
    TBA1000110.90.0110.016455545615
    TBA75019.70.0140.020400475535
    TBA60018.80.0180.024350420475
    57832450018.00.0220.028320380430
    TBA35017.00.0310.040260310350
    TBA25016.10.0430.055215255290
    5979581211.91.6602.075202020
    5799621012.11.0401.300303030
    569037812.20.6520.815405055
    569039612.50.4110.514556575
    569040412.90.2580.323708595
    569041213.30.1620.20395115130
    569042114.00.1290.161110130145