SPEC 45501

1/C CU 2000V EPR RHH/RHW-2 CPE Power Cable

Power Cable 2000Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 Chlorinated Polyethylene (CPE) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
  2. Binder Tape:Mylar Tape
  3. Insulation:Ethylene Propylene Rubber (EPR) Type RHH/RHW-2
  4. Overall Jacket:Cross-linked/Thermoset Chlorinated Polyethylene (CPE) Jacket

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1581 Electrical Wires, Cables and Flexible Cords
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power cables rated 2000 volts or less for the distribution of electrical energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE EXXXXX #P# (UL) [#AWG Or #kcmil] CU RHH/RHW-2 EPR/CPE 2000V For CT USE SUN. RES. For DIRECT BURIAL FT4 YEAR (NESC) [SEQUENTIAL FEET MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorInsul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/Kcmilinchmilinchmilinchlb/1000ftlb/1000ft
    TBA1/00.360650.490450.580326422
    TBA2/00.404650.534450.624411516
    TBA3/00.454650.584450.674518634
    TBA4/00.510650.640450.730653782
    TBA2500.558750.708450.798772920
    TBA3500.661750.811650.94110811289
    TBA5000.789750.939651.06915441785
    TBA7500.968901.148651.27823162629
    TBA10001.117901.297651.42730883442
    TBA20001.5831151.813952.00361756834

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceShort Circuit Current 6 CyclesAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmpAmp
    TBA1/04.68450.1020.1280.03324011125150170
    TBA2/05.010650.0810.1020.03230264145175195
    TBA3/05.413420.0640.0810.03138154165200225
    TBA4/05.816930.0510.0640.03048114195230260
    TBA2506.420000.0430.0550.03056845215255290
    TBA3507.528000.0310.0390.03079583260310350
    TBA5008.640000.0220.0280.029113690320380430
    TBA75010.260000.0140.0200.028170535400475535
    TBA100011.480000.0110.0160.027227380455545615
    TBA200016.0160000.0050.0100.027454759555665750