SPEC 45552

CU 600V PE PE Cable Color Method 1 Table 1 Traffic Signal IMSA 20-1

Multi-conductor nonshielded 600V Polyethylene Insulation, Polyethylene (PE) Jacket

...

Construction:

  1. Conductor:Solid or stranded annealed bare copper class B per ASTM B 3 and B8
  2. Insulation:Polyethylene PE
  3. Rip Chord:High strength rip chord for ease of jacket removal
  4. Separator:Polyester tape
  5. Jacket:Black polyethylene PE jacket

Applications and Features:

Southwire’s IMSA 20-1 cable meets the requirements of International Municipal Signal Association IMSA 20-1 specification. Rated for use in traffic signal, traffic control systems, underground conduit and aerial use where supported by a messenger. IMSA 20-1 600 Volt series cables run from the traffic light to the controller station The conductors are bare annealed copper solid or stranded class B and covered with an abrasion, sunlight and moisture resistant polyethylene jacket. The insulated conductors are twisted and wrapped with a polyester tape. A ripcord is added under the black polyethylene jacket for ease of removal. These cables are capable of operating continuously at a conductor temperature between -20°C and 75°C.

• Cable is manufactured by Southwire Company in their Waukegan, IL plant USA.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper Conductors
  • EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method
  • IMSA 20-1
  • Sample Print Legend:

    SOUTHWIRE® YEAR SIZE 600V IMSA 20-1 CABLE SEQUENTAIL FOOT MARK.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilConductorsNo.inchmilmilinchlb/1000ft
    TBA16210.05125450.28354
    TBA16270.05625450.29557
    TBA16310.05125450.31473
    TBA16370.05625450.33076
    TBA16410.05125450.34491
    TBA16470.05625450.36495
    TBA16510.05125450.376110
    TBA16570.05625450.395115
    TBA16710.05125450.406146
    TBA16770.05625450.428152
    TBA16910.05125450.470185
    TBA16970.05625450.496192
    TBA161210.05125450.548253
    TBA161270.05625450.578263
    58140214210.06425450.31854
    57892314310.06425450.33566
    TBA14270.07025450.33658
    58140314370.07025450.35470
    58140414410.06425450.36583
    58140614470.07025450.38689
    TBA14510.06425450.398104
    58140714570.07025450.422111
    58132914710.06425450.432135
    57892114770.07025450.459144
    TBA14910.06425600.503174
    TBA14970.07025600.565196
    581400141010.06425600.576201
    578926141210.06425600.593234
    581401141070.07025600.612214
    TBA141270.07025600.630243
    578925141610.06425600.656305
    TBA141670.07025600.698325
    579044142010.06425600.725372
    TBA142110.06425600.725390
    TBA142070.07025600.773396
    TBA142170.07025600.773418
    TBA12210.08025450.37279
    TBA12310.08025450.39396
    TBA12270.08725450.39479
    TBA12370.08725450.417102
    TBA12410.08025450.430123
    TBA12470.08725450.456131
    TBA12510.08025450.471155
    TBA12570.08725450.500165
    TBA12710.08025600.513214
    TBA12770.08725600.576226
    TBA12910.08025600.630275
    TBA12970.08725600.670291
    TBA121210.08025600.705351
    TBA121270.08725600.751372
    TBA121610.08025800.783462
    TBA121670.08725800.874511

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusDC Resistance @ 25°C
    ConductorsAWG/KcmilinchΩ/1000ft
    TBA1621.134.14
    TBA1621.184.18
    TBA1631.264.14
    TBA1631.324.18
    TBA1641.384.14
    TBA1641.464.18
    TBA1651.504.14
    TBA1651.584.18
    TBA1671.624.14
    TBA1671.714.18
    TBA1691.884.14
    TBA1691.984.18
    TBA16122.194.14
    TBA16122.314.18
    5814021421.272.57
    5789231431.342.57
    TBA1421.342.63
    5814031431.422.63
    5814041441.462.57
    5814061441.542.63
    TBA1451.592.57
    5814071451.692.63
    5813291471.732.57
    5789211471.842.63
    TBA1492.012.57
    TBA1492.262.63
    58140014102.302.57
    57892614122.372.57
    58140114102.452.63
    TBA14122.522.63
    57892514162.622.57
    TBA14162.792.63
    57904414202.902.57
    TBA14212.902.57
    TBA14203.092.63
    TBA14213.092.63
    TBA1221.491.62
    TBA1231.571.62
    TBA1221.581.66
    TBA1231.671.66
    TBA1241.721.62
    TBA1241.821.66
    TBA1251.881.62
    TBA1252.001.66
    TBA1272.051.62
    TBA1272.301.66
    TBA1292.521.62
    TBA1292.681.66
    TBA12122.821.62
    TBA12123.001.66
    TBA12163.131.62
    TBA12163.501.66