SPEC 46027

3/C CU 2.4kV 90 EPR ARMOR-X PVC MV-105 VFD

Type MV-105 Three Conductor Copper, 90 Mils Ethylene Propylene Rubber (EPR) Continuous Corrugated Welded Armor (Armor-X), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:90 Mils Ethylene Propylene Rubber (EPR)
  4. Grounding Conductor:3 Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  5. Filler:Wax paper filler
  6. Binder:Polypropylene tape
  7. Armor:Continuous Corrugated Welded Armor (Armor-X)
  8. Overall Jacket:Polyvinyl Chloride (PVC)

Applications and Features:

Southwire’s 2.4KV ARMOR-X are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE [SYMBOL - LIGHTING BOLT] #P# ARMOR-X (UL) 3/C [#AWG or #kcmil] CU 90 MILS EPR 2.4KV MV-105 FOR CT USE SUN. RES. FOR DIRECT BURIAL FT4 [-50°C] YEAR (NESC) [SEQUENTIAL FEET MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationGroundJacket ThicknessApprox. ODApprox. WeightMax Pull TensionMin Bending Radius
    AWG/KcmilinchinchNo. x AWGmilinchlb/1000ftlbinch
    89061520.2830.4933 x 10501.5301393159310.7
    55485510.3220.5323 x 8601.5901680200911.1
    8906161/00.3620.5723 x 8601.6601940253411.6
    8906172/00.4050.6153 x 8601.7902275319412.5
    TBA3/00.4560.6663 x 6601.9652796402713.8
    8906184/00.5120.7223 x 6602.1603314507815.1
    8906192500.5580.7783 x 6602.3203776600016.2
    8906203500.6610.8813 x 6752.4404926840017.1
    8906215000.7891.0093 x 4752.82067411200019.7
    TBA6000.8661.0863 x 4753.03078211440021.2
    8906227500.9681.1883 x 4853.17094531800022.2

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceShield Short Circuit Current 6 CyclesAllowable Ampacity Directly Buried 90/105°CAllowable Ampacity In Air 90/105°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ/1000ftAmpAmpAmp
    20.1620.2030.03415089180/190140/154
    10.1290.1610.03319029200/215160/180
    1/00.1020.1280.03224011230/245185/205
    2/00.0810.1020.03130264260/280215/240
    3/00.0640.0810.03038154295/320250/280
    4/00.0510.0640.03048114335/360285/320
    2500.0430.0550.02956845365/395320/355
    3500.0310.0390.02879583440/475395/440
    5000.0220.0280.027113690530/570485/545
    6000.0180.0240.027136428575/620535/600
    7500.0140.0200.026170535650/700615/685