SPEC 46102

1/C CU 5kV 115 NLEPR 133% SIMpull® PVC MV-105

Type MV-105 Single Copper Conductor, 115 mil No Lead Ethylene Propylene Rubber (NL-EPR) Insulation, 133% Insulation Level, Tape Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket
...

For more details, please download our PDF catalog sheet below:

Table 1 – Weights and Measurements
Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationDiameter Over Insulation ShieldJacket ThicknessApprox. ODApprox. WeightMax Pull TensionMin Bending RadiusConduit Size
AWG/Kcmilinchinchinchmilinchlb/1000ftlbinchinch
95463620.2830.5500.610650.7604545319.12.5
95464410.3220.5890.649650.7995226709.62.5
9550051/00.3620.6290.689650.83960984510.12.5
9550132/00.4050.6720.732650.882714106510.62.5
9550213/00.4560.7230.783800.963871134211.63
9550884/00.5120.7790.839801.0191034169312.23
9550392500.5580.8340.894801.0741180200012.93
9550473500.6610.9370.997801.1771540280014.13.5
9550545000.7891.0651.125801.3052067400015.74
9550967500.9681.2531.313801.4932932600017.95
95507010001.1171.4021.462801.6423777800019.75

All dimensions are nominal and subject to normal manufacturing tolerances

◊ Cable marked with this symbol is a standard stock item

Table 2 – Electrical and Engineering Data
Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive ReactanceInductive ReactanceZero Sequence ImpedancePositive Sequence ImpedanceShield Short Circuit Current 6 CyclesAllowable Ampacity In Duct 90/105°CAllowable Ampacity In Air 90/105°C
AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftMΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
20.1620.2030.0360.0440.568 + j0.5120.203 + j0.0442017145/155190/215
10.1290.1610.0330.0430.530 + j0.4900.162 + j0.0432144170/180225/250
1/00.1020.1280.0300.0410.498 + j0.4680.128 + j0.0412274195/210260/290
2/00.0810.1010.0270.0400.473 + j0.4460.102 + j0.0402414220/235300/330
3/00.0640.0810.0250.0390.452 + j0.4220.081 + j0.0392580250/270345/385
4/00.0510.0640.0230.0380.434 + j0.3970.065 + j0.0372762290/310400/445
2500.0430.0540.0220.0370.423 + j0.3750.055 + j0.0372941320/345445/495
3500.0310.0390.0190.0350.402 + j0.3360.040 + j0.0353276385/415550/615
5000.0220.0280.0160.0330.381 + j0.2960.029 + j0.0333693470/505695/775
7500.0140.0200.0140.0320.355 + j0.2470.020 + j0.0324304585/630900/1000
10000.0110.0160.0120.0310.336 + j0.2160.016 + j0.0304789670/7201075/1200