SPEC 48001

CU 600V LSZH XHHW-2 SOLONONplus®

SOLONONplus® 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type XHHW-2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:SOLONONplus® Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type XHHW-2

Applications and Features:

Southwire’s 600 Volt SOLONONplus® Type XHHW-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

a. The conductors are available in tinned and flexible copper stranding upon request.
b. NEC compliant
c. The halogen content is less than 0.2% and Acid gas less than 2.0%
d. Passes UL VW-1 # 8 AWG and larger
e. 70,000 BTU/Hr. Vertical Flame Test
f. UL listed for CT use on 1/0 and Larger
g. UL listed FT4 and ST-1 (limited smoke)
h. -40°C Cold impact and cold bend
i. Oil Resistant I and II
j. UV/Sunlight resistant black color
k. Color Available upon request

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • ICEA S-95-658 (NEMA WC70) Power cables rated 2000 volts or less for the distribution of electrical energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • ISO 14001 Environmental management systems standard
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways
  • Sample Print Legend:

    SOUTHWIRE SOLONONplus (TM) E30117 #P# (UL) [#AWG Or #kcmil] CU LSZH XLPO Type XHHW-2 -40°C PRI PRII 600V SEQUENTIAL FOOTAGE MARKS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    6495931410.064300.1241318
    6473611470.07300.131318
    5992541210.081300.1412027
    6496011270.087300.1472027
    5992631010.102300.1623240
    6465421070.111300.1713240
    599328870.139450.2295167
    599337670.174450.26481100
    599346470.221450.311129153
    599355270.277450.367205235
    6437521190.321550.431258297
    6416931/0190.360550.470326369
    5995092/0190.404550.514411459
    6416953/0190.454550.564518573
    5995194/0190.510550.620653715
    641699250370.558650.688772846
    641700350370.661650.79110811169
    641701500370.789650.91915441648
    641703600610.866801.02618531987
    TBA750610.968801.12823162465
    TBA1000611.117801.27730883257

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceShort Circuit Current 6 CyclesAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmpAmp
    649593140.5332.633.2880.036935151515
    647361140.5332.633.2880.036935151515
    599254120.6521.662.0750.0341485202020
    649601120.6521.662.0750.0341485202020
    599263100.7831.041.30.0322360293030
    646542100.7831.041.30.0322360293030
    59932880.91320.6520.8150.0333754404855
    59933761.12100.4110.5140.0315966556675
    59934641.23340.2580.3230.0309491708495
    59935521.55310.1620.2030.0281508996115130
    64375211.76700.1290.1620.02819029107128145
    6416931/01.98450.1020.1280.02824011126150170
    5995092/02.110650.0810.1020.02730264144172195
    6416953/02.313420.0640.0810.02738154167199225
    5995194/02.516930.0510.0640.02648114192230260
    6416992502.820000.0430.0550.02756845215257290
    6417003503.228000.0310.0400.02679583259310350
    6417015003.740000.0220.0290.025113690319381430
    6417036005.148000.0180.0180.024136428352421475
    TBA7505.660000.0140.0140.02170535397474535
    TBA10006.480000.0110.0110.017227380456545615