SPEC 70080

600V SEOPRENE® SEOOW Power Cord Non-UL/CSA with Black Jacket 105°C

600 Volt, 105°C Flexible Cord. Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant. Non UL / Non CSA Listed

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black TPE (other colors available upon request)

Applications and Features:

Southwire Type SEOOW Flexible Cords are permitted for indoor and outdoor temporary power uses, portable industrial machinery and compressors. Type SEOOW Cords are suitable for use in temperatures between -50°C to maximum 105°C.

Specifications:

  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    SOUTHWIRE® SEOPRENE® CORD 2/C 8 AWG (7.85mm2) SEOOW 600V - 50C TO 105C WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *DC Resistance
    AWG/KcmilCount# x AWGmilmilinchlb/1000ftAmpΩ/1000ft
    598323222208296/2848900.662243400.7
    550449223208396/2848900.701311400.7
    550450224208496/28481000.783408350.7
    551140224708596/28481000.851491280.7
    TBATBA6296/26481000.747336550.42
    550556223216396/26481000.818452550.42
    550405224216496/26481000.892579450.42
    598330225216596/26481050.987714360.42
    TBATBA4296/24461000.886503700.28
    598331223224396/24481100.913625700.28
    550404224224496/24481251.022821600.28
    598333225524596/24481251.117998480.28
    TBATBA22119/0.0223481201.084712950.17
    5539422232323119/0.0223501291.158985950.17
    5504732242324119/0.0223501291.261241800.17
    5505632255325119/0.0223501351.3961540640.17

    All dimensions are nominal and subject to normal manufacturing tolerances

    ◊ Cable marked with this symbol is a standard stock item

    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.

    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *DC Resistance
    AWG/KcmilCount# x AWGmmmmmmkg/kmAmpΩ/km
    598323222208296/281.222.2916.81362402.30
    550449223208396/281.222.2917.81463402.30
    550450224208496/281.222.5419.89607352.30
    551140224708596/281.222.5421.62731282.30
    TBATBA6296/261.222.5418.97500551.38
    550556223216396/261.222.5420.78673551.38
    550405224216496/261.222.5422.66862451.38
    598330225216596/261.222.6725.071063361.38
    TBATBA4296/241.172.5422.50749700.92
    598331223224396/241.222.7923.19930700.92
    550404224224496/241.223.1825.961222600.92
    598333225524596/241.223.1828.371485480.92
    TBATBA22119/0.02231.223.0527.531060950.56
    5539422232323119/0.02231.273.2829.411466950.56
    5504732242324119/0.02231.273.2832.001847800.56
    5505632255325119/0.02231.273.4335.462292640.56

    Color Code

    # of ConductorColor Sequence
    2Black, White
    3Black, White, Green
    4Black, White, Red, Green
    5Black, White, Red, Green, Orange

    Revision: 1.0.00M