SPEC 45003
1/C CU 600V XLPE RHH/RHW-2 USE-2 Power Cable
Power Cable 600Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 USE-2 CT Rated

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.
Specifications:
Sample Print Legend:
SOUTHWIRE EXXXXX #P# (UL) [#AWG Or #kcmil] CU RHH/RHW-2 XLPE 600V For CT USE SUN. RES. For DIRECT BURIAL FT4 VW-1YEAR (NESC) [SEQUENTIAL FEET MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
955872 | 2 | 7 | 0.277 | 60 | 0.403 | 205 | 243 |
890105 | 1/0 | 19 | 0.360 | 80 | 0.520 | 326 | 387 |
890106 | 2/0 | 19 | 0.404 | 80 | 0.564 | 411 | 479 |
890631 | 3/0 | 19 | 0.454 | 80 | 0.614 | 518 | 594 |
890107 | 4/0 | 19 | 0.510 | 80 | 0.670 | 653 | 738 |
890632 | 250 | 37 | 0.558 | 95 | 0.748 | 772 | 878 |
890108 | 350 | 37 | 0.661 | 95 | 0.851 | 1081 | 1205 |
890109 | 500 | 37 | 0.789 | 95 | 0.979 | 1544 | 1690 |
890633 | 750 | 61 | 0.968 | 110 | 1.188 | 2316 | 2514 |
TBA | 1000 | 61 | 1.117 | 110 | 1.337 | 3088 | 3313 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Shield Short Circuit Current 6 Cycles | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | Amp | |
955872 | 2 | 1.1 | 531 | 0.162 | 0.203 | 0.032 | 15089 | 125 | 150 | 170 |
890105 | 1/0 | 2.1 | 845 | 0.102 | 0.128 | 0.030 | 24011 | 125 | 150 | 170 |
890106 | 2/0 | 2.3 | 1065 | 0.081 | 0.102 | 0.029 | 30264 | 145 | 175 | 195 |
890631 | 3/0 | 2.5 | 1342 | 0.064 | 0.081 | 0.029 | 38154 | 165 | 200 | 225 |
890107 | 4/0 | 2.7 | 1693 | 0.051 | 0.064 | 0.028 | 48114 | 195 | 230 | 260 |
890632 | 250 | 3.0 | 2000 | 0.043 | 0.055 | 0.028 | 56845 | 215 | 255 | 290 |
890108 | 350 | 3.4 | 2800 | 0.031 | 0.040 | 0.028 | 79583 | 260 | 310 | 350 |
890109 | 500 | 3.9 | 4000 | 0.022 | 0.029 | 0.027 | 113690 | 320 | 380 | 430 |
890633 | 750 | 5.9 | 6000 | 0.014 | 0.020 | 0.026 | 170535 | 400 | 475 | 535 |
TBA | 1000 | 6.7 | 8000 | 0.011 | 0.016 | 0.026 | 227380 | 455 | 545 | 615 |
† Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Revision: 3.0.00C