SPEC 45008

1/C AL 600V XLPE RHH/RHW-2 USE-2 Power Cable

Power Cable 600Volt Single Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 USE-2

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2

Applications and Features:

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made 600V products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE EXXXXX #P# (UL) [#AWG Or #kcmil] AL RHH/RHW-2 USE-2 XLPE 600V For CT USE SUN. RES. For DIRECT BURIAL FT4 VW-1YEAR (NESC) [SEQUENTIAL FEET MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorInsul. ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/Kcmilinchmilinchlb/1000ftlb/1000ft
    27279960.336800.50499165
    27280740.336800.50499165
    27282320.336800.50499165
    27283110.336800.50499165
    5761421/00.336800.50499165
    2728562/00.376800.536125186
    2728643/00.423800.583158225
    5759914/00.475800.635199279
    5767872500.520950.710235339
    5759923000.570950.760282392
    2729144000.570950.760282392
    5965307000.570950.760282392
    TBA9000.570950.760282392
    5761373500.616950.809329452
    5673245000.736950.926471622
    5761416000.8051101.033565734
    5762197500.9081101.128706892
    TBA10001.0601101.2809411155
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    27279962.06340.1680.2110.031100120135
    27280742.06340.1680.2110.031100120135
    27282322.06340.1680.2110.031100120135
    27283112.06340.1680.2110.031100120135
    5761421/02.06340.1680.2110.031100120135
    2728562/02.17990.1330.1670.030115135150
    2728643/02.310070.1050.1320.029130155175
    5759914/02.512700.0840.1050.028150180205
    5767872502.815000.0710.0890.029170205230
    5759923003.018000.0590.0750.028195230260
    2729144003.018000.0590.0750.028195230260
    5965307003.018000.0590.0750.028195230260
    TBA9003.018000.0590.0750.028195230260
    5761373503.221000.0510.0640.028210250280
    5673245003.730000.0350.0450.027260310350
    5761416005.236000.0300.0380.027285340385
    5762197505.645000.0240.0310.027320385435
    TBA10006.460000.0180.0240.026375445500
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).