SPEC 45058

Multi-Conductor CU 600V PVC Type TC SDN Flexible Control Cable

Type TC-SDN® Control Cable 600 Volt Flexible Strand Bare Copper Conductors, Polyvinyl Chloride (PVC) insulation with nylon sheath THHN/THWN, Black Neoprene Jacket, Oil and Sunlight Resistant 90°C Dry 75°C Wet

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon sheath THHN/THWN. Color code Method 1 Table 2 with no white or green.
  3. Fillers:Polypropylene or paper to form round core
  4. Binder:Two mil mylar tape helically applied over core
  5. Jacket:Black heavy duty sunlight and oil resistant Neoprene

Applications and Features:

Southwire SDN (Small Diameter Neoprene) flexible control tray cables 600 Volt are suited for use in industrial power or control circuits where small diameter, flame retardant cables are desired. These cables are suitable for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Southwire SDN cables listed as THHN/THWN are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC Article 501 and 502. Southwire SDN flexible control cable is CSA listed Type TC and as Control and Instrumentation Cable Type (CIC)

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 66 Fixture Wire Type TFFN
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • Sample Print Legend:

    SOUTHWIRE{R} SDN XXX AWG (0.82mm2) XX/C TC 90{D}C DRY 75{D}C WET SUN RES 600V DIR BUR E75755 MASTER-DESIGN (UL) --- 156205 (CSA) CIC 90{D}C DRY 75{D}C WET PVC/N (-40{D}C) 600V SR OIL RES FT4
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODApprox. WeightDC ResistanceMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.inchmilmilinchlb/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    5699251830.04420450.29526.661.16777
    5699261850.04420450.334716.661.336777
    5841001850.04420450.334706.661.336777
    5699271860.04420450.36846.661.44777
    5699281880.04420450.365946.661.46777
    57134118100.04420500.4171166.661.668777
    56992918120.04420500.4421316.661.768777
    56994318140.04420500.4621496.661.848777
    57134218160.04420500.5151706.662.06777
    56994418190.04420600.5522086.662.208777
    57138918240.04420700.6512666.662.604666
    56993018370.04420700.743726.662.96666
    16 AWG
    5699121620.05820450.302544.181.208101010
    5713401630.05820450.313624.181.252101010
    5699141640.05820450.341754.181.364101010
    5699151650.05820450.372924.181.488101010
    5699161660.05820450.4021054.181.608101010
    5699171670.05820450.4021134.181.60891010
    5699181680.05820550.4571364.181.82891010
    56991016100.05820450.4641654.181.856679
    5700891690.05820550.4871504.181.94891010
    56991916120.05820600.5241924.182.096679
    57009016140.05820600.5682184.182.272679
    56992016160.05820600.5792424.182.316679
    56992216190.05820600.6282794.182.512679
    56991116240.05820650.673464.182.68678
    56992316300.05820700.7654314.183.06678
    56992416370.05820900.865454.183.44678
    14 AWG
    5699311430.07420450.344802.631.376151515
    5699321440.07420450.377992.631.508151515
    5699331450.07420450.4131212.631.652141515
    5699341460.07420450.4471392.631.788141515
    5700911480.07420650.5192012.632.076121515
    56993514100.07420650.5952332.632.3891112
    57009214120.07420650.6022652.632.40891112
    56993614160.07420650.6783412.632.71291112
    57009414240.07420700.7844892.633.1368911
    57009514370.07420900.9797542.633.916789
    12 AWG
    5699371230.09220450.3831151.651.532202020
    5699381240.09220450.4221401.651.688162020
    5699401250.09220450.4641761.651.856162020
    5699411260.09220450.5042081.652.016162020
    5699421280.09220800.622971.652.48141720
    57131312120.09220650.6884011.652.752101215
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)

    Revision: 3.0.00M