SPEC 45061
Multi-Conductor 600 or 1000 Volt Cu XLPE XHHW-2 CPE Jacket Control Cable Halo-Flex™ Type TC-ER-HL
Halo-Flex™ Type TC-ER-HL Control Cable 600 or 1000 Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 -40°C Thermoplastic CPE Jacket, Control Cable Conductor Identification Method 1 Table 2

Construction:
- Conductor:Flexible Stranded Rope-Lay Class K Copper per ASTM B174
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2, 30 Mils thick for all sizes
- Ground:Green insulated ground same size as phase conductor
- Filler:Polypropylene filler as needed to fill interstecies
- Rip Cord:Rip cord for quick removal of extruded polymeric layer and jacket
- Separator:Mylar for ease of stripability. Optional metal shield
- Extruded Polymeric Layer:Extruded Polymeric Fill Layer
- Overall Jacket:-40°C Thermoplastic Chlorinated Polyethylene CPE Jacket
Applications and Features:
Southwire’s Halo-Flex™ 600 or 1000 Volt Type TC-ER-HL power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. A gas/vapor-tight polymeric sheath is exturded over the core. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Listed for exposed runs in hazardous locations (TC-ER-HL) per NEC 336.10. - 40°C cold bend and cold impact. HALO-FLEX ™ CPE jacket is made with patented SIM Technology. Cable can be installed in conduit without the aid of lubrication. PATENT www.patentsw.com
Specifications:
Sample Print Legend:
SOUTHWIRE{R} HALO-FLEX{TM} TC-ER-HL E75755 {UL} XX AWG CU XX CDRS XHHW-2 GW 1 X XX AWG XLPE/CPE 90{D} C JACKET 600V or 1000V TYPE TC-ER-HL SUN. RES. FOR DIRECT BURIAL FT4 VW-1 -40{D}C OIL RES I & II ABS. RoHS-2 2011/65/EU COMPLIANT {YYYY} 07-KA180012-MSHA {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | ||||||
14 AWG | |||||||||||||||||||
679785 | 14 | 5 | 0.074 | 30 | 60 | 0.659 | 64 | 243 | 2.630 | 3.288 | 5.27 | 14 | 15 | 15 | |||||
679789 | 14 | 6 | 0.074 | 30 | 60 | 0.659 | 77 | 260 | 2.630 | 3.288 | 5.27 | 14 | 15 | 15 | |||||
679792 | 14 | 7 | 0.074 | 30 | 60 | 0.702 | 90 | 290 | 2.630 | 3.288 | 5.62 | 12 | 15 | 15 | |||||
12 AWG | |||||||||||||||||||
679804 | 12 | 5 | 0.092 | 30 | 60 | 0.71 | 102 | 306 | 1.660 | 2.075 | 5.68 | 16 | 20 | 20 | |||||
679807 | 12 | 6 | 0.092 | 30 | 60 | 0.71 | 122 | 331 | 1.660 | 2.075 | 5.68 | 16 | 20 | 20 | |||||
679810 | 12 | 7 | 0.092 | 30 | 60 | 0.758 | 143 | 371 | 1.660 | 2.075 | 6.06 | 14 | 20 | 20 | |||||
10 AWG | |||||||||||||||||||
679841 | 10 | 5 | 0.116 | 30 | 60 | 0.782 | 162 | 404 | 1.040 | 1.300 | 6.26 | 24 | 28 | 30 | |||||
679844 | 10 | 6 | 0.116 | 30 | 60 | 0.782 | 194 | 442 | 1.040 | 1.300 | 6.26 | 24 | 28 | 30 | |||||
679848 | 10 | 7 | 0.116 | 30 | 60 | 0.877 | 227 | 532 | 1.040 | 1.300 | 7.02 | 21 | 24 | 28 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Revision: 3.0.00M