SPEC 45255
3/C CU 600V EPR XHHW-2 CPE Power Cable With Ground
Type TC-ER Power Cable 600Volt Three Conductor Copper, Ethylene Propylene Rubber (EPR) insulation XHHW-2 Chlorinated Polyethylene (CPE) Jacket with 1 Tinned CU Ground. VW-1 Rated

Construction:
- Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2. VW-1 Rated
- Grounding Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Overall Jacket:Chlorinated Polyethylene (CPE) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} XX AWG (XX.X{mm2}) 3/C EPR/CPE TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG TINNED E75755 MASTER-DESIGN {UL} 600V 90{D}C DRY/90{D}C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V 90{D}C USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
591981◊ | 8 | 7 | 0.139 | 45 | 0.229 | 1 x 10 | 60 | 0.615 | 187 | 319 |
591983◊ | 6 | 7 | 0.174 | 45 | 0.264 | 1 x 8 | 60 | 0.691 | 297 | 458 |
591985◊ | 4 | 7 | 0.221 | 45 | 0.311 | 1 x 8 | 60 | 0.791 | 442 | 624 |
591987◊ | 2 | 7 | 0.277 | 45 | 0.367 | 1 x 6 | 80 | 0.953 | 703 | 965 |
591989◊ | 1 | 19 | 0.321 | 55 | 0.431 | 1 x 6 | 80 | 1.091 | 865 | 1188 |
591991◊ | 1/0 | 19 | 0.360 | 55 | 0.470 | 1 x 6 | 80 | 1.175 | 1069 | 1428 |
591993◊ | 2/0 | 19 | 0.404 | 55 | 0.514 | 1 x 6 | 80 | 1.270 | 1327 | 1728 |
591995 | 3/0 | 19 | 0.454 | 55 | 0.564 | 1 x 4 | 80 | 1.378 | 1700 | 2150 |
591996◊ | 4/0 | 19 | 0.510 | 55 | 0.620 | 1 x 4 | 80 | 1.499 | 2110 | 2617 |
591998◊ | 250 | 37 | 0.558 | 65 | 0.688 | 1 x 4 | 80 | 1.646 | 2469 | 3063 |
592000◊ | 350 | 37 | 0.661 | 65 | 0.791 | 1 x 3 | 110 | 1.929 | 3440 | 4263 |
592002 | 500 | 37 | 0.789 | 65 | 0.919 | 1 x 2 | 110 | 2.205 | 4885 | 5877 |
674038 | 500 | 37 | 0.789 | 65 | 0.919 | 1 x 3/0 | 110 | 2.224 | 4885 | 5976 |
TBA | 750 | 61 | 0.968 | 80 | 1.128 | 1 x 1 | 110 | 2.656 | 7278 | 8617 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Shield Short Circuit Current 6 Cycles | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | Amp | |
591981◊ | 8 | 2.5 | 396 | 0.652 | 0.815 | 0.033 | 3754 | 40 | 50 | 55 |
591983◊ | 6 | 2.8 | 630 | 0.411 | 0.514 | 0.031 | 5966 | 55 | 65 | 75 |
591985◊ | 4 | 3.2 | 1002 | 0.258 | 0.323 | 0.030 | 9491 | 70 | 85 | 95 |
591987◊ | 2 | 3.8 | 1593 | 0.162 | 0.203 | 0.028 | 15089 | 95 | 115 | 130 |
591989◊ | 1 | 5.5 | 2009 | 0.129 | 0.162 | 0.028 | 19029 | 110 | 130 | 145 |
591991◊ | 1/0 | 5.9 | 2534 | 0.102 | 0.128 | 0.028 | 24011 | 125 | 150 | 170 |
591993◊ | 2/0 | 6.4 | 3194 | 0.081 | 0.102 | 0.027 | 30264 | 145 | 175 | 195 |
591995 | 3/0 | 6.9 | 4027 | 0.064 | 0.081 | 0.027 | 38154 | 165 | 200 | 225 |
591996◊ | 4/0 | 7.5 | 5078 | 0.051 | 0.064 | 0.026 | 48114 | 195 | 230 | 260 |
591998◊ | 250 | 8.2 | 6000 | 0.043 | 0.055 | 0.027 | 56845 | 215 | 255 | 290 |
592000◊ | 350 | 9.6 | 8400 | 0.031 | 0.040 | 0.026 | 79583 | 260 | 310 | 350 |
592002 | 500 | 13.2 | 12000 | 0.022 | 0.029 | 0.025 | 113690 | 320 | 380 | 430 |
674038 | 500 | 13.2 | 12000 | 0.022 | 0.029 | 0.025 | 113690 | 320 | 380 | 430 |
TBA | 750 | 15.9 | 18000 | 0.014 | 0.020 | 0.025 | 170535 | 400 | 475 | 535 |
† Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Revision: 3.0.00C