SPEC 45258

4/C CU 600 or 1000 V XLPE XHHW-2 PVC Jacket Power Cable With Ground. Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX KCMIL (XXX{mm2}) CU 4/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
    557009870.139450.2291 x 10600.673238379
    560102670.174450.2641 x 8600.758379551
    556993470.221450.3111 x 8800.910572800
    554303270.277450.3671 x 6801.0479101189
    6020111190.321550.4311 x 6801.20011261472
    5544361/0190.360550.4701 x 6801.29513981784
    5569852/0190.404550.5141 x 6801.40117422173
    6020373/0190.454550.5641 x 4801.52122232708
    5544444/0190.510550.6201 x 41101.72227703410
    602052250370.558650.6881 x 41101.88132493992
    TBA350370.661650.7911 x 2/01102.08147805661
    602078350370.661650.7911 x 31102.08145315416
    644547^350370.661650.7911 x 31102.08145315416
    675713350370.661650.7911 x 11102.08146275508
    675711500370.789650.8961 x 2/01102.38264987724
    554469500370.789650.8961 x 21102.38264457516
    672237500370.789650.8961 x 1/01102.38364457638
    672235500370.789650.8961 x 11102.38364987570
    672240500370.789650.8961 x 4/01102.51064457955
    675706600610.866801.0261 x 1/01402.75676939224
    649649600610.866801.0261 x 4/01402.90376939565
    675708600610.866801.0261 x 2501402.90376939718
    570961750610.968801.1281 x 11403.003961811224
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    55700982.75280.6520.8150.036324044
    56010263.08400.4110.5140.034445260
    55699343.613360.2580.3230.033566876
    55430325.221240.1620.2030.0317692104
    60201116.026780.1290.1610.03288104116
    5544361/06.533790.1020.1280.031100120136
    5569852/07.042590.0810.1010.030116140156
    6020373/07.653700.0640.0800.030132160180
    5544444/08.767710.0510.0640.029156184208
    6020522509.480000.0430.0540.030172204232
    TBA35012.8112000.0310.0390.029208248280
    60207835012.8112000.0310.0390.029208248280
    644547^35012.8112000.0310.0390.029208248280
    67571335012.8112000.0310.0390.029208248280
    67571150014.6160000.0220.0270.028256304344
    55446950014.6160000.0220.0270.028256304344
    67223750014.6160000.0220.0270.028256304344
    67223550014.6160000.0220.0270.028256304344
    67224050014.6160000.0220.0270.028256304344
    67570660016.5192000.0180.0230.029282336380
    64964960017.4192000.0180.0230.029282336380
    67570860017.4192000.0180.0230.029282336380
    57096175018.0240000.0140.0190.028320380428
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.

    Revision: 3.0.00C