SPEC 45263

3/C AL 600V PVC THHN PVC Power Cable With Ground. Silicone Free

Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG AL 3 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 3 AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA870.134350.1941 x 8450.53163146
    671383670.169370.2431 x 8600.66391220
    TBA470.213460.2931 x 6600.779144313
    675613270.268460.3481 x 6800.938214454
    5880231190.299570.3991 x 4801.052278578
    675618^1190.299570.3991 x 4801.052278578
    6756201/0190.336570.4361 x 4801.132341673
    6756222/0190.376570.4761 x 3801.218418877
    6756243/0190.423570.5231 x 4801.320518929
    5782184/0190.475570.5751 x 2801.4326661126
    673253^4/0190.475570.5751 x 2801.4326661126
    583386250370.520680.6401 x 2801.5777751332
    675626^250370.520680.6401 x 2801.5777751332
    TBA300370.570680.6901 x 2801.6859181528
    TBA350370.616680.7361 x 21101.84410601821
    678099500370.736680.8561 x 11102.10415072420
    599317600610.805790.9631 x 6001102.49817924205
    673497^600610.805790.9631 x 6001102.49817924205
    677400750610.908791.0481 x 3/01102.52322913521
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA82.12971.0701.3450.030354045
    67138362.74720.6750.8480.029405055
    TBA43.17510.4240.5330.029556575
    67561323.811940.2660.3340.0287590100
    58802315.315060.2110.2650.02885100115
    675618^15.315060.2110.2650.02885100115
    6756201/05.719010.1680.2110.028100120135
    6756222/06.123960.1330.1670.027115135150
    6756243/06.630200.1050.1320.027130155175
    5782184/07.238090.0840.1050.026150180205
    673253^4/07.238090.0840.1050.026150180205
    5833862507.945000.0710.0890.026170205230
    675626^2507.945000.0710.0890.026170205230
    TBA3008.454000.0590.0750.026195230260
    TBA3509.263000.0510.0640.026210250280
    67809950012.690000.0350.0450.025260310350
    59931760015.0108000.0300.0380.025285340385
    673497^60015.0108000.0300.0380.025285340385
    67740075015.1135000.0240.0310.025320385435
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.