SPEC 45263
3/C AL 600V PVC THHN PVC Power Cable With Ground
Type TC-ER Power Cable 600Volt Three Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG AL 3 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 2 AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
TBA | 8 | 7 | 0.134 | 35 | 0.194 | 1 x 8 | 45 | 0.531 | 63 | 146 |
TBA | 6 | 7 | 0.169 | 35 | 0.229 | 1 x 8 | 60 | 0.636 | 90 | 208 |
TBA | 4 | 7 | 0.213 | 46 | 0.293 | 1 x 6 | 60 | 0.779 | 144 | 313 |
675613 | 2 | 7 | 0.268 | 46 | 0.348 | 1 x 6 | 80 | 0.938 | 214 | 454 |
675618 | 1 | 19 | 0.299 | 57 | 0.399 | 1 x 4 | 80 | 1.052 | 278 | 578 |
675620 | 1/0 | 19 | 0.336 | 57 | 0.436 | 1 x 4 | 80 | 1.132 | 341 | 673 |
675622 | 2/0 | 19 | 0.376 | 57 | 0.476 | 1 x 3 | 80 | 1.218 | 418 | 877 |
675624 | 3/0 | 19 | 0.423 | 57 | 0.523 | 1 x 4 | 80 | 1.320 | 518 | 929 |
673253 | 4/0 | 19 | 0.475 | 57 | 0.575 | 1 x 2 | 80 | 1.432 | 666 | 1126 |
675626 | 250 | 37 | 0.520 | 68 | 0.640 | 1 x 2 | 80 | 1.577 | 775 | 1332 |
TBA | 300 | 37 | 0.570 | 68 | 0.690 | 1 x 2 | 80 | 1.685 | 918 | 1528 |
TBA | 350 | 37 | 0.616 | 68 | 0.736 | 1 x 2 | 110 | 1.844 | 1060 | 1821 |
678099 | 500 | 37 | 0.736 | 68 | 0.856 | 1 x 1 | 110 | 2.104 | 1507 | 2420 |
673497 | 600 | 61 | 0.805 | 79 | 0.963 | 1 x 600 | 110 | 2.498 | 1792 | 4205 |
677400 | 750 | 61 | 0.908 | 79 | 1.048 | 1 x 3/0 | 110 | 2.523 | 2291 | 3521 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Shield Short Circuit Current 6 Cycles | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | Amp | |
TBA | 8 | 2.1 | 297 | 1.070 | 1.345 | 0.030 | 3785 | 35 | 40 | 45 |
TBA | 6 | 2.5 | 472 | 0.675 | 0.848 | 0.029 | 6016 | 40 | 50 | 55 |
TBA | 4 | 3.1 | 751 | 0.424 | 0.533 | 0.029 | 9569 | 55 | 65 | 75 |
675613 | 2 | 3.8 | 1194 | 0.266 | 0.334 | 0.028 | 15213 | 75 | 90 | 100 |
675618 | 1 | 5.3 | 1506 | 0.211 | 0.265 | 0.028 | 19186 | 85 | 100 | 115 |
675620 | 1/0 | 5.7 | 1901 | 0.168 | 0.211 | 0.028 | 24209 | 100 | 120 | 135 |
675622 | 2/0 | 6.1 | 2396 | 0.133 | 0.167 | 0.027 | 30513 | 115 | 135 | 150 |
675624 | 3/0 | 6.6 | 3020 | 0.105 | 0.132 | 0.027 | 38468 | 130 | 155 | 175 |
673253 | 4/0 | 7.2 | 3809 | 0.084 | 0.105 | 0.026 | 48509 | 150 | 180 | 205 |
675626 | 250 | 7.9 | 4500 | 0.071 | 0.089 | 0.026 | 57313 | 170 | 205 | 230 |
TBA | 300 | 8.4 | 5400 | 0.059 | 0.075 | 0.026 | 68775 | 195 | 230 | 260 |
TBA | 350 | 9.2 | 6300 | 0.051 | 0.064 | 0.026 | 80238 | 210 | 250 | 280 |
678099 | 500 | 12.6 | 9000 | 0.035 | 0.045 | 0.025 | 114625 | 260 | 310 | 350 |
673497 | 600 | 15.0 | 10800 | 0.030 | 0.038 | 0.025 | 137550 | 285 | 340 | 385 |
677400 | 750 | 15.1 | 13500 | 0.024 | 0.031 | 0.025 | 171938 | 320 | 385 | 435 |
† Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Revision: 3.0.00C