SPEC 45264

AL 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Sunlight resistant Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE® {UL} XXX AWG AL 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG AL 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {YYYY} PC09-FLRBLGN {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    5822388370.134451 x 8600.66662189
    TBA6370.169451 x 8600.68189227
    6716334370.212451 x 6600.886144394
    TBA2370.268451 x 6800.935213449
    6709712360.268451 x 6800.983214523
    6750181380.298551 x 4801.109278610
    TBA1/03190.336551 x 4801.125338658
    6709631/03100.336551 x 4801.173341755
    6466722/03120.376551 x 4801.209419782
    5996193/03150.422551 x 4801.324518918
    6720574/03190.474551 x 2801.4236671105
    6466672503220.520651 x 1801.5647931323
    6722573003210.569651 x 21101.7539191602
    1378803503350.615651 x 11101.84410781788
    5822204003350.659651 x 3/01101.96013012060
    5632115003350.735651 x 11102.09015062298
    5822235003350.735651 x 2/01102.10315532438
    6722595003350.735651 x 4/01102.20016282540
    6714945003350.735651 x 2501102.21316652635
    5821296003580.812801 x 1/01102.30418132881
    6794016003580.812801 x 3501102.54920453166
    5875737503580.908801 x 1/01102.52622413430
    5800137503580.908801 x 3/01102.52623003392
    5799247503580.908803 x 2/01102.52625203963
    6713927503580.908801 x 4001102.58525213756
    TBA10003611.060801 x 1/01402.91729454528
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    582238832.72971.0721.2900.052354045
    TBA632.74720.6740.8120.051405055
    671633433.57510.4240.5100.048556575
    TBA233.711940.2670.3210.0457590100
    670971233.911940.2670.3210.0457590100
    675018135.515060.2110.2540.04685100115
    TBA1/035.619000.1680.2010.044100120135
    6709631/035.919000.1680.2010.044100120135
    6466722/036.023950.1330.1600.043115135150
    5996193/036.630200.1050.1260.042130155175
    6720574/037.138080.0840.1000.041150180205
    64666725037.845000.0710.0860.041170205230
    67225730038.854000.0590.0710.041195230260
    13788035039.263000.0500.0620.040210250280
    58222040039.872000.0440.0540.040225270305
    563211500312.590000.0350.0440.039260310350
    582223500312.690000.0350.0440.039260310350
    672259500313.290000.0350.0440.039260310350
    671494500313.390000.0350.0440.039260310350
    582129600313.8108000.0290.0370.039285340385
    679401600315.3108000.0290.0370.039285340385
    587573750315.2135000.0240.0310.038320385435
    580013750315.2135000.0240.0310.038320385435
    579924750315.2135000.0240.0310.038320385435
    671392750315.5135000.0240.0310.038320385435
    TBA1000317.5180000.0180.0250.037375445500
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Method 4 Color Code. (1-ONE, 2-TWO, 3-THREE)

    Stock CodeSize
    6716334
    6709712
    6709631/0

    Revision: 1.000.005

    Updated On: Jan. 24, 2024, 6:13 p.m. UTC