SPEC 45264

3/C AL 600V or 1000 V XLPE XHHW-2 PVC Power Cable With Ground. Silicone Free.

Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG AL 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG AL 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {YYYY} PC09-FLRBLGN {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
    582238870.134450.2241 x 8600.60463180
    582131670.169450.2591 x 8600.67990230
    TBA470.213450.3031 x 6600.774144311
    582120270.268450.3581 x 6800.933214452
    TBA1190.299550.4091 x 4801.043278572
    TBA1/0190.336550.4461 x 4801.123341666
    5803762/0190.376550.4861 x 4801.210418779
    5996193/0190.423550.5331 x 4801.311518922
    5803774/0190.475550.5851 x 2801.4246661118
    582222250370.520650.6501 x 1801.5647751318
    TBA300370.570650.7001 x 2801.6729181513
    596550350370.616650.7461 x 11101.83110601820
    582220400350.659650.7891 x 3/01101.89413011943
    582223500370.736650.8661 x 2/01102.02415072468
    563211500370.736650.8661 x 11102.09115072401
    582129600580.805800.9651 x 1/01102.30418132873
    679401600610.805800.9651 x 3/01102.54920463166
    677353600610.805800.9653 x 1/0802.56823873937
    587573750610.908801.0681 x 1/01102.52722403478
    580013750610.908801.0681 x 3/01102.52723003368
    579924750610.908801.0683 x 2/01102.52725203715
    671392750610.908801.0681 x 4001102.58525213747
    TBA1000611.06801.211 x 1/01402.92729514424
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    58223882.42971.0701.3450.034354045
    58213162.74720.6750.8480.032405055
    TBA43.17510.4240.5330.030556575
    58212023.711940.2660.3340.0287590100
    TBA15.215060.2110.2650.02985100115
    TBA1/05.619010.1680.2110.028100120135
    5803762/06.023960.1330.1670.028115135150
    5996193/06.630200.1050.1320.027130155175
    5803774/07.138090.0840.1050.026150180205
    5822222507.845000.0710.0890.027170205230
    TBA3008.454000.0590.0750.026195230260
    5965503509.263000.0510.0640.026210250280
    5822204009.263000.430.5260.040225270305
    58222350012.590000.0350.0450.025260310350
    56321150012.590000.0350.0450.025260310350
    58212960013.8108000.0300.0380.026285340385
    67940160015108000.0300.0380.026285340385
    67735360015108000.0300.0380.026285340385
    58757375015.2135000.0240.0310.025320385435
    58001375015.2135000.0240.0310.025320385435
    57992475015.2135000.0240.0310.025320385435
    67139275015.5135000.0240.0310.025320385435
    TBA100020.5180000.0180.0240.025375445500
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Revision: 3.0.00C