SPEC 45265

4/C AL 600V XLPE XHHW-2 PVC Power Cable With Ground. Silicone Free

Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG (XX{mm2}) 3E AL 4/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG 3E AL 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA870.134450.2241 x 8600.66178218
    TBA670.169450.2591 x 8600.745115281
    TBA470.213450.3031 x 6800.891184415
    TBA270.268450.3581 x 6801.024277557
    TBA1190.299550.4091 x 4801.147358706
    TBA1/0190.336550.4461 x 4801.237441827
    TBA2/0190.376550.4861 x 4801.333545972
    6722513/0190.423550.5331 x 4801.4476781156
    5837274/0190.475550.5851 x 2801.5728671402
    582123250370.520650.6501 x 11101.78910291772
    672252300370.570650.7001 x 21101.90914081952
    582124350370.616650.7461 x 1/01102.02114282305
    578537400370.659650.7921 x 11102.13116012505
    582121400370.659650.7921 x 3/01102.23716012584
    582125500370.736650.8661 x 2/01102.31120273080
    578536500370.736650.8661 x 11102.31119823035
    596549500370.736650.8661 x 3/01102.43420623209
    582126500370.736650.8661 x 2501102.47021413281
    582127600610.813800.9731 x 3501102.7226163981
    582250600610.813800.9731 x 4/01102.72024853812
    578538750610.908801.0681 x 1/01402.85829534575
    580014750610.908801.0681 x 3/01402.85830104625
    TBA900610.999801.1591 x 1/01403.0934874625
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA82.63961.0701.3450.037283236
    TBA63.06300.6750.8480.035324044
    TBA43.610020.4240.5330.033445260
    TBA25.115930.2660.3340.032607280
    TBA15.720090.2110.2650.032688092
    TBA1/06.225340.1680.2110.0318096108
    TBA2/06.731940.1330.1670.03192108120
    6722513/07.240270.1050.1320.030104124140
    5837274/07.950780.0840.1050.030120144164
    5821232508.960000.0710.0890.030136164184
    6722523001272000.05780.07250.029195230260
    58212435012.184000.0510.0640.029168200224
    57853740013.996000.0440.470.029180216244
    58212140013.996000.0440.470.029180216244
    58212550013.9120000.0350.0450.029208248280
    57853650013.9120000.0350.0450.029208248280
    59654950014.6120000.0350.0450.029208248280
    58212650014.9120000.0350.0450.029208248280
    58212760016.3144000.0300.0370.029228272308
    58225060016.2144000.0300.0370.029228272308
    57853875017.1180000.0240.0300.029256308348
    58001475017.1180000.0240.0300.029256308348
    TBA90018.5216000.0200.0210.025284340384
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Revision: 3.0.00C