SPEC 45266
4/C AL 600V XLPE XHHW-2 LSZH Power Cable With Ground
Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 SOLONON® Low Smoke Zero Halogen (LSZH) Jacket with 1 Bare AL Ground

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:SOLONON® Low Smoke Zero Halogen (LSZH) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
SOUTHWIRE EXXXXX #P# (UL) [#AWG Or #kcmil] AL XHHW-2 XLPE/LSZH 600V Type TC-ER For CT USE SUN. RES. For DIRECT BURIAL FT4 [-25°C] YEAR (NESC) [SEQUENTIAL FEET MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
TBA | 8 | 7 | 0.134 | 45 | 0.224 | 1 x 8 | 60 | 0.661 | 78 | 212 |
TBA | 6 | 7 | 0.169 | 45 | 0.259 | 1 x 8 | 60 | 0.745 | 115 | 273 |
TBA | 4 | 7 | 0.213 | 45 | 0.303 | 1 x 6 | 80 | 0.891 | 184 | 408 |
TBA | 2 | 7 | 0.268 | 45 | 0.358 | 1 x 6 | 80 | 1.024 | 277 | 549 |
TBA | 1 | 19 | 0.299 | 55 | 0.409 | 1 x 4 | 80 | 1.147 | 358 | 691 |
TBA | 1/0 | 19 | 0.336 | 55 | 0.446 | 1 x 4 | 80 | 1.237 | 441 | 810 |
TBA | 2/0 | 19 | 0.376 | 55 | 0.486 | 1 x 4 | 80 | 1.333 | 545 | 953 |
TBA | 3/0 | 19 | 0.423 | 55 | 0.533 | 1 x 4 | 80 | 1.447 | 678 | 1135 |
TBA | 4/0 | 19 | 0.475 | 55 | 0.585 | 1 x 2 | 80 | 1.572 | 867 | 1378 |
TBA | 250 | 37 | 0.520 | 65 | 0.650 | 1 x 1 | 110 | 1.789 | 1029 | 1772 |
TBA | 350 | 37 | 0.616 | 65 | 0.746 | 1 x 1 | 110 | 2.021 | 1408 | 2285 |
TBA | 500 | 37 | 0.736 | 65 | 0.866 | 1 x 1 | 110 | 2.311 | 1982 | 2997 |
TBA | 750 | 61 | 0.908 | 80 | 1.068 | 1 x 1/0 | 140 | 2.858 | 2953 | 4520 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Shield Short Circuit Current 6 Cycles | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | Amp | |
TBA | 8 | 2.6 | 396 | 1.070 | 1.345 | 0.037 | 3785 | 28 | 32 | 36 |
TBA | 6 | 3.0 | 630 | 0.675 | 0.848 | 0.035 | 6016 | 32 | 40 | 44 |
TBA | 4 | 3.6 | 1002 | 0.424 | 0.533 | 0.033 | 9569 | 44 | 52 | 60 |
TBA | 2 | 5.1 | 1593 | 0.266 | 0.334 | 0.032 | 15213 | 60 | 72 | 80 |
TBA | 1 | 5.7 | 2009 | 0.211 | 0.265 | 0.032 | 19186 | 68 | 80 | 92 |
TBA | 1/0 | 6.2 | 2534 | 0.168 | 0.211 | 0.031 | 24209 | 80 | 96 | 108 |
TBA | 2/0 | 6.7 | 3194 | 0.133 | 0.167 | 0.031 | 30513 | 92 | 108 | 120 |
TBA | 3/0 | 7.2 | 4027 | 0.105 | 0.132 | 0.030 | 38468 | 104 | 124 | 140 |
TBA | 4/0 | 7.9 | 5078 | 0.084 | 0.105 | 0.030 | 48509 | 120 | 144 | 164 |
TBA | 250 | 8.9 | 6000 | 0.071 | 0.089 | 0.030 | 57313 | 136 | 164 | 184 |
TBA | 350 | 12.1 | 8400 | 0.051 | 0.064 | 0.029 | 80238 | 168 | 200 | 224 |
TBA | 500 | 13.9 | 12000 | 0.035 | 0.045 | 0.029 | 114625 | 208 | 248 | 280 |
TBA | 750 | 17.1 | 18000 | 0.024 | 0.030 | 0.029 | 171938 | 256 | 308 | 348 |
† Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Revision: 3.0.00C