SPEC 45273

3/C 600 or 1000 Volt Cu (FR-XLPE) XHHW-2 TCu Braid Thermoplastic CPE-TP Jacket Power Cable Halo-Flex™ Type TC-ER-HL

Halo-Flex™ Type TC-ER-HL Power Cable 600 or 1000 Volt Copper Conductors, Cross Linked Polyethylene (FR-XLPE) Insulation XHHW-2 -40°C Tinned Copper Braid Shield Thermoplastic CPE-TP Jacket, Control Cable Conductor Identification Method 3

...

Construction:

  1. Conductor:Flexible Stranded Rope-Lay Class I Copper per ASTM B172
  2. Insulation:Fire Retardant Cross Linked Polyethylene (FR-XLPE) Type XHHW-2
  3. Ground:Three symmetrical bare grounds flexible strand
  4. Filler:Non-Hygroscopic flame retardant fillers
  5. Shield:Tinned copper braid shield
  6. Rip Cord:Rip cord for quick removal of extruded polymeric layer and jacket
  7. Extruded Polymeric Layer:Extruded Polymeric Barrier Layer
  8. Overall Jacket:Low-Friction SIM Technology® -40°C Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Applications and Features:

Southwire’s Halo-Flex™ 600V TC-ER-HL or 1000V TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. A gas/vapor-tight polymeric sheath is extruded over the core. Rated for use in Class I, II, or III, Division 1 & 2, Zone 1 & 2, hazardous locations per NEC Article 501, 502, and 503. Listed for exposed runs (TC-ER-HL) per NEC 336.10. - 40°C cold bend and cold impact. HALO-FLEX ™ CPE jacket is made with patented SIM Technology. Cable can be installed in conduit without the aid of lubrication. PATENT www.patentsw.com

Sample Print Legend:

{SQFTG} SOUTHWIRE{R} HALO-FLEX{TM} TC-ER-HL E75755 {UL} XX AWG CU 3 CDRS XHHW-2 GW 3 X XX AWG TCU BRAID XLPE/CPE 90{D}C JACKET 600V TYPE TC-ER-HL or 1000V TYPE TC-ER SUN. RES. FOR DIRECT BURIAL FT4 -40{D}C OIL RES I & II ABS RoHS-3 2015/863 COMPLIANT {YYYY} 07-KA180012-MSHA
Table 1 – Weights and Measurements
Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
AWG/KcmilNo. of StrandsinchmilinchNo. x AWGmilinchlb/1000ftlb/1000ft
66955141120.235470.3293 x 12841.038508862
66955721680.315470.4093 x 10841.1677621173
6695631/02590.385580.5013 x 10841.40911491699
6695692/03240.42580.5363 x 10841.50214152003
6695753/04180.47580.5863 x 8841.59318142444
6695814/05320.535550.6453 x 81161.78422233034
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC, 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Table 2 – Electrical and Engineering Data
Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
AWG/KcmilinchlbΩ/1000ftΩ/1000ftAmpAmpAmp
669551412.510020.27430.3568708595
66955721415930.13660.177795115130
6695631/016.925340.10910.142125150170
6695692/01831940.08680.1129145175195
6695753/019.140270.06880.0895165200225
6695814/021.450780.05470.0711195230260
† Ampacities are based on Table 310.16 of the NEC, 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)

Revision: