SPEC 45307

4/C CU 600V XLPE XHHW-2 AIA PVC Power Cable With Ground. Silicone Free

Type MC Power Cable 600Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:Aluminum Interlocked Armor (AIA)
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE MASTER-DESIGN {UL} 4/C (XX AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90{D}C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGinchmilinchlb/1000ftlb/1000ft
    TBA870.139450.2291 x 100.763500.863238486
    574460670.174450.2641 x 80.848500.948379665
    TBA470.221450.3111 x 80.960501.060572911
    580730270.277450.3671 x 61.097501.2039101276
    TBA1190.321550.4311 x 61.250501.35011261618
    8902291/0190.360550.4701 x 61.345501.44513981940
    TBA2/0190.404550.5141 x 61.451501.55117422341
    TBA3/0190.454550.5641 x 41.571601.69122232922
    5626054/0190.498550.6081 x 41.786601.90627703626
    557959250370.542650.6881 x 41.940602.06032494144
    551452350370.661650.7911 x 32.219602.33945315696
    TBA350370.661650.7911 x 2/02.219602.45647795944
    605410500370.789650.9191 x 22.528752.67864457903
    563407600610.866801.0261 x 22.787752.93776939418
    672989600610.866801.0261 x 4/02.799832.96581469680
    TBA750610.968801.1281 x 13.033853.203961811605
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA86.05280.6520.8150.036324044
    57446066.68400.4110.5140.034445260
    TBA47.413360.2580.3230.033566876
    58073028.421240.1620.2030.0317692104
    TBA19.526780.1290.1610.03288104116
    8902291/010.133790.1020.1280.031100120136
    TBA2/010.942590.0810.1010.030116140156
    TBA3/011.853700.0640.0800.030132160180
    5626054/012.867710.0510.0640.029156184208
    55795925023.380000.0430.0540.030172204232
    55145235016.4112000.0310.0390.029208248280
    TBA35019.7112000.0310.0390.029208248280
    60541050018.7160000.0220.0270.028256304344
    56340760020.6192000.0180.0230.029282336380
    67298960023.7100000.0180.0230.029282336380
    TBA75022.4240000.0140.0190.028320380428
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.

    Revision: 3.0.00C