SPEC 45402

1/C AL 2000V XLPE RHH/RHW-2 Power Cable BLACK SSRTM Type PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Aluminum Conductor XLPE Insulation. Sizes 6AWG through 1000 kcmil. Heat, Moisture, and Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation:Southwire’s Super Sunlight Resistant (SSRTM) Cross-linked Polyethylene (XLPE)

Applications and Features:

Southwire’s new Super Sunlight Resistant – SSR Type PV cables are leading the industry with features such as enhanced UV stability, color permanence and aged physical properties, providing you with the most reliable solutions for your PV wiring systems. The cable is available in sizes 6 AWG through 1000 kcmil. The product is approved for use in solar power applications per the NEC article 690 and is rated 90°C for exposed or concealed wiring in wet or dry locations. Individual conductors are stranded aluminum alloy covered with a cross-linked polyethylene (XLPE) insulation and is rated for direct burial. The cable is sunlight resistant, RoHS compliant, passes -40°C cold bend.

Specifications:

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 4703 Standard for Photovoltaic Wire
  • AA 8176 Stranded Aluminum Alloy Conductors
  • Sample Print Legend:

    SOUTHWIRE SSRTM E316464 (UL) PV WIRE XX AWG (XX.X mm2) COMPACT AL.— ALUMAFLEX® AA8176 2000V 90°C WET OR DRY (-40 ?C) SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V — RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    643576670.169850.3392555
    643580470.213850.3833975
    643583180.2991050.50979138
    6435871/0100.3361050.546100164
    6435902/0120.3761050.586125196
    6435943/0160.4231050.633158235
    6435974/0190.4751050.685199284
    641821250220.521200.76236342
    641818300350.571200.81283398
    641815350350.6161200.856330452
    641812400350.6591200.899377507
    641492500350.7361200.976471614
    641495600580.8131351.083572751
    641499750580.9081351.178707902
    6419301000581.061351.339421166
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzShield Short Circuit Current 6 CyclesAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmpAmp
    64357662.711570.6610.8480.0386016405055
    64358043.062500.4160.5330.0359569556575
    64358314.073980.2070.2650.0341918685100115
    6435871/04.376340.1640.2110.03324209100120135
    6435902/04.697990.130.1670.03230513115135150
    6435943/05.0610070.1030.1320.03138468130155175
    6435974/05.4812700.0820.1050.0348509150180205
    6418212506.0815000.06940.0890.0357313170205230
    6418183006.4818000.05780.0750.0368775195230260
    6418153506.8521000.04950.0640.02980238210250280
    6418124007.1924000.04340.0560.02991700225270305
    6414925007.8130000.03470.0450.028114625260310350
    6414956008.6636000.02890.0380.028137550285340385
    6414997509.4245000.02310.0310.028171938320385435
    641930100010.6460000.01730.0240.027229250375445500
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)

    Revision: 3.0.00M